Standard Series Twin Socket Outlet White Electric
Item Number: 414-WE
Retail
N/A
RRP (Inc. GST)
Datasheet

For 414-WE
Close
Specifications
Design
Product or component type
socket-outlet
Product brand
Clipsal
Physical
Quantity per set
set of 2
Marking
without marking
Local signalling
without light indicator
Device mounting
surface
Fixing mode
by screws
[in] rated current
10 A
[ue] rated operational voltage
250 V AC
Depth
63 mm
Length
72 mm
Width
65 mm
Fixing center
50 mm
Number of poles
1
Standards
- AS/NZS 3112
- AS 3100
- AS 3109
Reach regulation
Reference contains Substances of Very High Concern above the threshold
Eu rohs directive
Compliant with Exemptions
Mercury free
Yes
Rohs exemption information
Yes
China rohs regulation
Product out of China RoHS scope. Substance declaration for your information
Material
Material
plastic
Documents & downloads
hide showFilter items
-
All
-
CAD Files and Packs
-
Product Brochures
-
Technical Data Catalogues
-
Installation Instruction
-
Specification Guide
-
Declaration of Conformity
-
Certificates (MSDS)
Frequently Asked Questions
hide showIssue:
How do you calculate the DC bus voltage using the "Mains Voltage" (ULn) displayed in the Monitor menu
How do you calculate the DC bus voltage using the "Mains Voltage" (ULn) displayed in the Monitor menu
Product Line:
ATV61, ATV71, ATV312, ATV12, ATV32
ATV61, ATV71, ATV312, ATV12, ATV32
Environment:
All models and serial numbers
All models and serial numbers
Cause:
None
None
Resolution:
These drives do a calculation using the measured DC bus voltage to estimate the mains voltage (line supply). The drive measures the DC Bus internally and divides it by 1.414 (square root of 2) and then displays it as the Mains Voltage (ULn) In the monitor menu.
So, when given ULn, simply multiply by 1.414 to get the measured DC bus voltage value.
These drives do a calculation using the measured DC bus voltage to estimate the mains voltage (line supply). The drive measures the DC Bus internally and divides it by 1.414 (square root of 2) and then displays it as the Mains Voltage (ULn) In the monitor menu.
So, when given ULn, simply multiply by 1.414 to get the measured DC bus voltage value.
Issue:
Looking to monitor or read the DC bus on the ATV61 drive HMI.
Product Line:
Altivar 61/71 ATV61 ATV71
Environment:
All
Cause:
Limited access to terminals
Resolution:
There are no monitoring options for reading the DC Bus from the drive HMI.
In the monitor menu it will display "Mains Voltage".
To calculate the DC Bus voltage:
If you multiply this value by 1.414 (sq root of 2) the result will be the value of the DC bus.
However, the drive does a calculation with the DC bus voltage to determine the mains voltage (line supply).
Looking to monitor or read the DC bus on the ATV61 drive HMI.
Product Line:
Altivar 61/71 ATV61 ATV71
Environment:
All
Cause:
Limited access to terminals
Resolution:
There are no monitoring options for reading the DC Bus from the drive HMI.
In the monitor menu it will display "Mains Voltage".
To calculate the DC Bus voltage:
If you multiply this value by 1.414 (sq root of 2) the result will be the value of the DC bus.
However, the drive does a calculation with the DC bus voltage to determine the mains voltage (line supply).