TeSys D, Time delay Auxiliary Contact Block, TeSys Deca, 1NO + 1NC, on delay 0.3-3s, front, screw clamp terminals

Home ProductsIndustrialTeSysTime delay Auxiliary Contact Block

TeSys D, Time delay Auxiliary Contact Block, TeSys Deca, 1NO + 1NC, on delay 0.3-3s, front, screw clamp terminals

Item Number: LADT0

TeSys Deca time delay auxiliary contact block, for contactors LC1D, LC1F and control relays CAD. It provides 1NO+1NC contacts rated up to 10A 690V AC, On-delay setting range 0.3-3s, connection by screw clamp terminals. Clip-on front mounting, it procures high reliability and durability. Multi standards certified (IEC, UL, CSA, CCC, EAC), Green Premium compliant (RoHs/Reach).

Datasheet

Product Dimensions

Width icon

Width44 mm

Height icon

Height48 mm

Depth icon

Depth61 mm

Barcode

Qty UoM EAN Colour
-
-
-

Specifications

Design

Range

TeSys|TeSys Deca

Range of product

TeSys Deca

Product or component type

time delay auxiliary contact block

Sustainable offer status

Green Premium product

Physical

Range compatibility

TeSys Deca CAD|TeSys Deca LC1D|TeSys F LC1F|TeSys F CR1F

[ue] rated operational voltage

690 V AC 25...400 Hz

[ie] rated operational current

6 A at 120 V AC-15|1.04 A at 690 V AC-15|0.55 A at 125 V DC-13|0.1 A at 600 V DC-13

Standards

EN/IEC 60947-5-1|UL 60947-5-1|CSA C22.2 No 60947-5-1|GB/T 14048.5|EN 50012|IEC 60335-1:Clause 30.2|IEC 60335-2-40:Annex JJ|UL 60335-2-40:Annex JJ

Product certifications

IECEE CB Scheme|UL|CSA|CCC|EAC|UKCA

Protection type

gG fuse 10 A

Mechanical durability

5 Mcycles

Insulation resistance

> 10 MOhm

Connections - terminals

screw clamp terminals 1 cable(s) 1-2.5 mm²flexible with cable end|screw clamp terminals 1 cable(s) 1-2.5 mm²flexible without cable end|screw clamp terminals 2 cable(s) 1-2.5 mm²flexible with cable end|screw clamp terminals 2 cable(s) 1-2.5 mm²flexible without cable end|screw clamp terminals 1 cable(s) 1-2.5 mm²rigid|screw clamp terminals 2 cable(s) 1-2.5 mm²rigid|screw clamp terminals

Height

48 mm

Width

44 mm

Depth

61 mm

Environmental characteristic

normal environment

Ip degree of protection

IP20 conforming to IEC 60529

Ambient air temperature for storage

-60...80 °C

Ambient air temperature for operation

-40...70 °C

Reach regulation

Reference contains Substances of Very High Concern above the threshold

Eu rohs directive

Compliant with Exemptions

Mercury free

Yes

Rohs exemption information

Yes

China rohs regulation

Product out of China RoHS scope. Substance declaration for your information

Environmental disclosure

ENVPEP110702EN_V01

Circularity profile

N/A

California proposition 65

WARNING: Cancer - www.P65Warnings.ca.gov

Others

Life cycle assessment data

Yes

Substance regulation data deliverable

Yes

Package 1 bare product quantity

1

Package 2 bare product quantity

140

Package 3 bare product quantity

1120

Product name

TeSys Deca

Mounting location

front

Pole contact composition

1 NO + 1 NC

Auxiliary contacts operation

time delay

Timer type

on delay

Time delay range

0.3...3 s

[ui] rated insulation voltage

690 V conforming to IEC 60947-5-1|600 V conforming to UL 60947-5-1|600 V conforming to CSA C22.2 No 60947-5-1

[ith] conventional free air thermal current

10 A (at 60 °C)

Irms rated making capacity

140 A at <= 690 V AC conforming to IEC 60947-5-1|250 A at <= 690 V DC conforming to IEC 60947-5-1

Permissible short-time rating

100 A 60 °C 1 s|120 A 60 °C 500 ms|140 A 60 °C 100 ms

Minimum switching current

5 mA

Minimum switching voltage

17 V

Non-overlap time

1.5 ms on de-energisation no overlap between NC and NO contact|1.5 ms on energisation no overlap between NC and NO contact

Tightening torque

1.7 N.m - with screwdriver flat Ø 6 mm|1.7 N.m - with screwdriver Philips No 2|1.7 N.m - with screwdriver pozidriv No 2

Shielding continuity terminal

without

Protective treatment

TH conforming to IEC 60068

Operating altitude

3000 m

Unit type of package 1

PCE

Number of units in package 1

1

Package 1 height

5.200 cm

Package 1 width

6.500 cm

Package 1 length

5.000 cm

Package 1 weight

74.000 g

Unit type of package 2

S03

Number of units in package 2

140

Package 2 height

30.000 cm

Package 2 width

30.000 cm

Package 2 length

40.000 cm

Package 2 weight

11.018 kg

Unit type of package 3

P06

Number of units in package 3

1120

Package 3 height

75.000 cm

Package 3 width

60.000 cm

Package 3 length

80.000 cm

Package 3 weight

101.340 kg

Sustainable packaging

Yes

Weee

The product must be disposed on European Union markets following specific waste collection and never end up in rubbish bins

Pvc free

Yes
Show all specifications

Documents & downloads

hide show
Filter items
  • All

  • CAD Files and Packs

  • Technical Data Catalogues

  • Environmental Disclosure

  • Installation Instruction

  • Technical Drawing

  • Certificates (MSDS)

  • Declaration of Conformity

  • eTechPub

Frequently Asked Questions

hide show

Will the LAD** time delay auxiliary contact module fit the D2 series pre-Tesys contactors?

Issue:
Can new accessories be used on older style contactors

Product Line:
IEC contactors and starters

Environment:
Pre-Tesys Contactors

Cause:
Identifying product compatibility

Resolution:
Yes, all front mount D2 and Tesys series auxiliary modules are backward forward compatible.