TeSys GV2, Motor circuit breaker, TeSys Deca, 3P, 17 to 23A, thermal magnetic, screw clamp terminals, rotary handle

Home ProductsIndustrialTeSysMotor circuit breaker

TeSys GV2, Motor circuit breaker, TeSys Deca, 3P, 17 to 23A, thermal magnetic, screw clamp terminals, rotary handle

Item Number: GV2P21

TeSys GV motor circuit breaker, 3 poles (3P), 23A/690V, for 3-phase motor applications 9kW@400V. It provides a thermal-magnetic protection with a thermal setting range 17-23A, magnetic tripping at 13xIn, high breaking capacity Icu 50kA@400V. Connection by screw clamp terminals. Start-stop control by rotary knob guaranteed for 100 000 cycles AC-3. Multi standards certified (IEC, UL, CSA, CCC, EAC, Marine, ATEX), Green Premium compliant (RoHS/REACh).

Datasheet

Product Dimensions

Width icon

Width45 mm

Height icon

Height89 mm

Depth icon

Depth97 mm

Barcode

Qty UoM EAN Colour
-
-
-

Specifications

Design

Range

TeSys Deca

Range of product

TeSys GV2

Product or component type

motor circuit breaker

Device application

motor protection

Sustainable offer status

Green Premium product

Warranty

18 months

Physical

Fixing mode

35 mm symmetrical DIN rail: clipped|panel: screwed (with 2 x M4 screws)

Control type

rotary handle

[in] rated current

23 A

[ue] rated operational voltage

690 V AC 50/60 Hz conforming to IEC 60947-2

Mechanical durability

100000 cycles

Electrical durability

100000 cycles for AC-3 at 415 V In|100000 cycles for AC-3e at 415 V In

Width

45 mm

Height

89 mm

Depth

97 mm

Product certifications

CCC|UL|CSA|EAC|ATEX|LROS (Lloyds register of shipping)|BV|RINA|DNV-GL|UKCA

Ik degree of protection

IK04

Ip degree of protection

IP20 conforming to IEC 60529

Climatic withstand

conforming to IACS E10

Ambient air temperature for storage

-40...80 °C

Ambient air temperature for operation

-20...60 °C

Reach regulation

Free of Substances of Very High Concern above the threshold

Reach free of svhc

Yes

Eu rohs directive

Compliant with Exemptions

Rohs exemption information

Yes

China rohs regulation

Product out of China RoHS scope. Substance declaration for your information

Environmental disclosure

ENVPEP2211002

Circularity profile

ENVEOLI2211002

California proposition 65

WARNING: This product can expose you to chemicals including: Antimony oxide & Antimony trioxide, which is known to the State of California to cause cancer. For more information go to www.P65Warnings.ca.gov

Others

Package 1 bare product quantity

1

Package 2 bare product quantity

20

Package 3 bare product quantity

320

Product name

TeSys GV2|TeSys Deca

Device short name

GV2P

Trip unit technology

thermal-magnetic

Poles description

3P

Network type

AC

Utilisation category

category A conforming to IEC 60947-2|AC-3 conforming to IEC 60947-4-1|AC-3e conforming to IEC 60947-4-1

Network frequency

50/60 Hz conforming to IEC 60947-4-1

Motor power kw

9 kW at 400/415 V AC 50/60 Hz|11 kW at 500 V AC 50/60 Hz|18.5...18.5 kW at 690 V AC 50/60 Hz

Breaking capacity

100 kA Icu at 230/240 V AC 50/60 Hz conforming to IEC 60947-2|50 kA Icu at 400/415 V AC 50/60 Hz conforming to IEC 60947-2|20 kA Icu at 440 V AC 50/60 Hz conforming to IEC 60947-2|10 kA Icu at 500 V AC 50/60 Hz conforming to IEC 60947-2|4 kA Icu at 690 V AC 50/60 Hz conforming to IEC 60947-2

[ics] rated service short-circuit breaking capacity

100 % at 230/240 V AC 50/60 Hz conforming to IEC 60947-2|50 % at 400/415 V AC 50/60 Hz conforming to IEC 60947-2|75 % at 440 V AC 50/60 Hz conforming to IEC 60947-2|75 % at 500 V AC 50/60 Hz conforming to IEC 60947-2|100 % at 690 V AC 50/60 Hz conforming to IEC 60947-2

Thermal protection adjustment range

17...23 A conforming to IEC 60947...4-1

Magnetic tripping current

327 A

[ith] conventional free air thermal current

23 A conforming to IEC 60947-4-1

[ui] rated insulation voltage

690 V AC 50/60 Hz conforming to IEC 60947-2

[uimp] rated impulse withstand voltage

6 kV conforming to IEC 60947-2

Phase failure sensitivity

yes conforming to IEC 60947-4-1

Suitability for isolation

yes conforming to IEC 60947-1 § 7-1-6

Power dissipation per pole

2.5 W

Maximum operating rate

25 cyc/h

Rated duty

continuous conforming to IEC 60947-4-1

Direct connector

without

Tightening torque

1.7 N.m - on screw clamp terminal

Compatibility code

GV2P

Fire resistance

960 °C conforming to IEC 60695-2-11

Mechanical robustness

shocks: 30 Gn for 11 ms|vibrations: 5 Gn, 5...150 Hz

Operating altitude

2000 m

Unit type of package 1

PCE

Number of units in package 1

1

Package 1 height

4.800 cm

Package 1 width

9.300 cm

Package 1 length

10.000 cm

Package 1 weight

335.000 g

Unit type of package 2

S02

Number of units in package 2

20

Package 2 height

15.000 cm

Package 2 width

30.000 cm

Package 2 length

40.000 cm

Package 2 weight

6.926 kg

Unit type of package 3

P06

Number of units in package 3

320

Package 3 height

75.000 cm

Package 3 width

60.000 cm

Package 3 length

80.000 cm

Package 3 weight

118.816 kg

Weee

The product must be disposed on European Union markets following specific waste collection and never end up in rubbish bins
Show all specifications

Documents & downloads

hide show
Filter items
  • All

  • CAD Files and Packs

  • Technical Data Catalogues

  • Environmental Disclosure

  • End of Life Manual

  • Installation Instruction

  • Data Bulletin

  • Operating Manuals

  • Technical Drawing

  • Certificates (MSDS)

  • Declaration of Conformity

  • eTechPub