TeSys K, Control Relay, 3NO+2NC, 0 to 690V, 32VAC 50/60Hz standard coil, screw clamp

TeSys K, Control Relay, 3NO+2NC, 0 to 690V, 32VAC 50/60Hz standard coil, screw clamp

Item Number: CAD32C7

Datasheet

Product Dimensions

Width icon

Width45 mm

Height icon

Height77 mm

Depth icon

Depth84 mm

Barcode

Qty UoM EAN Colour
-
-
-

Specifications

Design

Range

TeSys

Range of product

TeSys D control relay

Product or component type

control relay

Sustainable offer status

Green Premium product

Warranty

18 months

Physical

[ue] rated operational voltage

<= 690 V AC 25...400 Hz

Mounting support

plate|rail

Connections - terminals

screw clamp terminals 1 cable(s) 1-4 mm²flexible without cable end|screw clamp terminals 2 cable(s) 1-4 mm²flexible without cable end|screw clamp terminals 1 cable(s) 1-4 mm²flexible with cable end|screw clamp terminals 2 cable(s) 1-2.5 mm²flexible with cable end|screw clamp terminals 1 cable(s) 1-4 mm²solid without cable end|screw clamp terminals 2 cable(s) 1-4 mm²solid without cable end

Mechanical durability

30 Mcycles

Insulation resistance

> 10 MOhm

Height

77 mm

Width

45 mm

Depth

84 mm

Net weight

0.58 kg

Standards

EN/IEC 60947-5-1|GB/T 14048.5|UL 60947-5-1|CSA C22.2 No 60947-5-1|JIS C8201-5-1

Product certifications

CB|CCC|UL|CSA|EAC|CE|UKCA

Ip degree of protection

IP2X front face conforming to VDE 0106

Ambient air temperature for operation

-40...60 °C|60...70 °C with derating

Ambient air temperature for storage

-60...80 °C

Reach regulation

Reference contains Substances of Very High Concern above the threshold

Eu rohs directive

Compliant with Exemptions

Mercury free

Yes

Rohs exemption information

Yes

China rohs regulation

Product out of China RoHS scope. Substance declaration for your information

Environmental disclosure

ENVPEP1501004

Circularity profile

ENVEOLI1501004

California proposition 65

"WARNING: This product can expose you to chemicals including: Antimony oxide & Antimony trioxide, which is known to the State of California to cause cancer. For more information go to www.P65Warnings.ca.gov"

Others

Package 1 bare product quantity

1

Product name

TeSys CAD

Device short name

CAD

Contactor application

control circuit

Utilisation category

AC-14|AC-15|DC-13

Pole contact composition

3 NO + 2 NC

Control circuit type

AC at 50/60 Hz

[uc] control circuit voltage

32 V AC 50/60 Hz

[uimp] rated impulse withstand voltage

6 kV conforming to IEC 60947

[ith] conventional free air thermal current

10 A (at 60 °C)

Irms rated making capacity

140 A AC conforming to IEC 60947-5-1|250 A DC conforming to IEC 60947-5-1

[icw] rated short-time withstand current

100 A - 1 s|120 A - 500 ms|140 A - 100 ms

Associated fuse rating

10 A gG conforming to IEC 60947-5-1

[ui] rated insulation voltage

600 V UL certified|600 V CSA certified|690 V conforming to IEC 60947-5-1

Tightening torque

1.2 N.m - on screw clamp terminals - with screwdriver Philips No 2|1.2 N.m - on screw clamp terminals - with screwdriver flat Ø 6 mm

Control circuit voltage limits

0.3...0.6 Uc (-40-70 °C):drop-out AC 50/60 Hz|0.8...1.1 Uc (-40-60 °C):operational AC 50 Hz|0.85...1.1 Uc (-40-60 °C):operational AC 60 Hz|1...1.1 Uc (60-70 °C):operational AC 50/60 Hz

Operating time

12...22 ms coil energisation and NO closing|4...12 ms coil de-energisation and NO opening|4...19 ms coil energisation and NC opening|6...17 ms coil de-energisation and NC closing

Maximum operating rate

180 cyc/mn

Inrush power in va

70 VA 50 Hz (at 20 °C)

Hold-in power consumption in va

8 VA 50 Hz (at 20 °C)

Minimum switching voltage

17 V

Minimum switching current

5 mA

Non-overlap time

1.5 ms on energisation between NC and NO contact|1.5 ms on de-energisation between NC and NO contact

Mechanical robustness

shocks control relay open: 10 Gn for 11 ms conforming to IEC 60068-2-27|shocks control relay closed: 15 Gn for 11 ms conforming to IEC 60068-2-27|vibrations control relay open: 2 Gn, 5...300 Hz conforming to IEC 60068-2-6|vibrations control relay closed: 4 Gn, 5...300 Hz conforming to IEC 60068-2-6

Compatibility code

CAD

Protective treatment

TH conforming to IEC 60068

Operating altitude

0...3000 m

Unit type of package 1

PCE

Number of units in package 1

1

Package 1 height

9.4 cm

Package 1 width

8.1 cm

Package 1 length

5.4 cm

Package 1 weight

300.0 g

Weee

The product must be disposed on European Union markets following specific waste collection and never end up in rubbish bins
Show all specifications

Documents & downloads

hide show
Filter items
  • All

  • CAD Files and Packs

  • Technical Data Catalogues

  • Installation Instruction

  • End of Life Manual

  • Environmental Disclosure

  • Certificates (MSDS)

  • Declaration of Conformity