TeSys D, Contactor, TeSys Deca, 4P(4 NO), AC-1, <= 440V, 32A, 48V AC 50/60Hz coil, screw terminal

TeSys D, Contactor, TeSys Deca, 4P(4 NO), AC-1, <= 440V, 32A, 48V AC 50/60Hz coil, screw terminal

Item Number: LC1DT32E7

Datasheet

Product Dimensions

Width icon

Width45 mm

Height icon

Height91 mm

Depth icon

Depth99 mm

Barcode

Qty UoM EAN Colour
-
-
-

Specifications

Design

Range

TeSys|TeSys Deca

Range of product

TeSys Deca

Product or component type

contactor

Sustainable offer status

Green Premium product

Warranty

18 months

Physical

[ue] rated operational voltage

power circuit: <= 690 V AC 25...400 Hz|power circuit: <= 300 V DC

[ie] rated operational current

32 A (at <60 °C) at <= 440 V AC AC-1 for power circuit

Mechanical durability

15 Mcycles

Electrical durability

1 Mcycles 32 A AC-1 at Ue <= 440 V

Connections - terminals

control circuit: screw clamp terminals 2 1-2.5 mm² - cable stiffness: flexible with cable end|control circuit: screw clamp terminals 1 1-4 mm² - cable stiffness: flexible without cable end|control circuit: screw clamp terminals 2 1-4 mm² - cable stiffness: flexible without cable end|control circuit: screw clamp terminals 1 1-4 mm² - cable stiffness: flexible with cable end|control circuit: screw clamp terminals 1 1-4 mm² - cable stiffness: solid without cable end|control circuit: screw clamp terminals 2 1-4 mm² - cable stiffness: solid without cable end|power circuit: screw clamp terminals 1 2.5-10 mm² - cable stiffness: flexible without cable end|power circuit: screw clamp terminals 2 2.5-10 mm² - cable stiffness: flexible without cable end|power circuit: screw clamp terminals 1 2.5-10 mm² - cable stiffness: flexible with cable end|power circuit: screw clamp terminals 2 2.5-10 mm² - cable stiffness: flexible with cable end|power circuit: screw clamp terminals 1 2.5-16 mm² - cable stiffness: solid without cable end|power circuit: screw clamp terminals 2 2.5-16 mm² - cable stiffness: solid without cable end

Insulation resistance

> 10 MOhm for signalling circuit

Mounting support

plate|rail

Standards

CSA C22.2 No 14|EN 60947-4-1|EN 60947-5-1|IEC 60947-4-1|IEC 60947-5-1|UL 508|IEC 60335-1

Product certifications

DNV|GL|CCC|LROS (Lloyds register of shipping)|RINA|BV|GOST|UL|CSA|CB

Ip degree of protection

IP20 front face conforming to IEC 60529

Climatic withstand

conforming to IACS E10 exposure to damp heat| conforming to IEC 60947-1 Annex Q category D exposure to damp heat

Height

91 mm

Width

45 mm

Depth

99 mm

Net weight

0.425 kg

Reach regulation

Reference contains Substances of Very High Concern above the threshold

Eu rohs directive

Compliant

Toxic heavy metal free

Yes

Mercury free

Yes

Rohs exemption information

Yes

China rohs regulation

 Pro-active China RoHS declaration (out of China RoHS legal scope)

Environmental disclosure

ENVPEP1501004

Circularity profile

ENVEOLI1501004

California proposition 65

WARNING: This product can expose you to chemicals including: Antimony oxide & Antimony trioxide, which is known to the State of California to cause cancer. For more information go to www.P65Warnings.ca.gov

Others

Life cycle assessment data

Yes

Substance regulation data deliverable

Yes

Package 1 bare product quantity

1

Package 2 bare product quantity

16

Device short name

LC1D

Contactor application

resistive load

Utilisation category

AC-1|AC-3|AC-3e|AC-4

Poles description

4P

[uc] control circuit voltage

48 V AC 50/60 Hz

Compatibility code

LC1D

Pole contact composition

4 NO

Protective cover

with

[ith] conventional free air thermal current

10 A (at 60 °C) for signalling circuit|32 A (at 60 °C) for power circuit

Irms rated making capacity

140 A AC for signalling circuit conforming to IEC 60947-5-1|250 A DC for signalling circuit conforming to IEC 60947-5-1|300 A at 440 V for power circuit conforming to IEC 60947

Rated breaking capacity

300 A at 440 V for power circuit conforming to IEC 60947

[icw] rated short-time withstand current

40 A 40 °C - 10 min for power circuit|84 A 40 °C - 1 min for power circuit|145 A 40 °C - 10 s for power circuit|240 A 40 °C - 1 s for power circuit|100 A - 1 s for signalling circuit|120 A - 500 ms for signalling circuit|140 A - 100 ms for signalling circuit

Associated fuse rating

10 A gG for signalling circuit conforming to IEC 60947-5-1|50 A gG at <= 690 V coordination type 1 for power circuit|35 A gG at <= 690 V coordination type 2 for power circuit

Average impedance

2.5 mOhm - Ith 32 A 50 Hz for power circuit

Power dissipation per pole

2.5 W AC-1

[ui] rated insulation voltage

power circuit: 600 V CSA certified|power circuit: 600 V UL certified|signalling circuit: 690 V conforming to IEC 60947-1|signalling circuit: 600 V CSA certified|signalling circuit: 600 V UL certified|power circuit: 690 V conforming to IEC 60947-4-1

Overvoltage category

III

Pollution degree

3

[uimp] rated impulse withstand voltage

6 kV conforming to IEC 60947

Safety reliability level

B10d = 1369863 cycles contactor with nominal load conforming to EN/ISO 13849-1|B10d = 20000000 cycles contactor with mechanical load conforming to EN/ISO 13849-1

Control circuit type

AC at 50/60 Hz

Coil technology

without built-in suppressor module

Control circuit voltage limits

0.3...0.6 Uc (-40-70 °C):drop-out AC 50/60 Hz|0.8...1.1 Uc (-40-60 °C):operational AC 50 Hz|0.85...1.1 Uc (-40-60 °C):operational AC 60 Hz|1...1.1 Uc (60-70 °C):operational AC 50/60 Hz

Inrush power in va

70 VA 60 Hz cos phi 0.75 (at 20 °C)|70 VA 50 Hz cos phi 0.75 (at 20 °C)

Hold-in power consumption in va

7.5...7.5 VA 60 Hz cos phi 0.3 (at 20 °C)|7 VA 50 Hz cos phi 0.3 (at 20 °C)

Heat dissipation

2...3 W at 50/60 Hz

Operating time

4...19 ms opening|12...22 ms closing

Maximum operating rate

3600 cyc/h 60 °C

Tightening torque

control circuit: 1.7 N.m - on screw clamp terminals - with screwdriver flat Ø 6 mm|control circuit: 1.7 N.m - on screw clamp terminals - with screwdriver Philips No 2|control circuit: 1.7 N.m - on screw clamp terminals - with screwdriver pozidriv No 2|power circuit: 1.8 N.m - on screw clamp terminals - with screwdriver flat Ø 6 mm|power circuit: 1.8 N.m - on screw clamp terminals - with screwdriver Philips No 2|power circuit: 1.8 N.m - on screw clamp terminals - with screwdriver pozidriv No 2

Auxiliary contact composition

1 NO + 1 NC

Auxiliary contacts type

type mechanically linked 1 NO + 1 NC conforming to IEC 60947-5-1| type mirror contact 1 NC conforming to IEC 60947-4-1

Signalling circuit frequency

25...400 Hz

Minimum switching voltage

17 V for signalling circuit

Minimum switching current

5 mA for signalling circuit

Non-overlap time

1.5 ms on de-energisation between NC and NO contact|1.5 ms on energisation between NC and NO contact

Contact compatibility

M6

Protective treatment

TH conforming to IEC 60068-2-30

Permissible ambient air temperature around the device

-40...60 °C|60...70 °C with derating

Operating altitude

0...3000 m

Fire resistance

850 °C conforming to IEC 60695-2-1

Flame retardance

V1 conforming to UL 94

Mechanical robustness

vibrations contactor open (2 Gn, 5...300 Hz) |vibrations contactor closed (4 Gn, 5...300 Hz) |shocks contactor closed (15 Gn for 11 ms) |shocks contactor open (8 Gn for 11 ms)

Unit type of package 1

PCE

Number of units in package 1

1

Package 1 height

5.500 cm

Package 1 width

9.500 cm

Package 1 length

12.000 cm

Package 1 weight

469.000 g

Unit type of package 2

S02

Number of units in package 2

16

Package 2 height

15.000 cm

Package 2 width

30.000 cm

Package 2 length

40.000 cm

Package 2 weight

7.998 kg

Weee

The product must be disposed on European Union markets following specific waste collection and never end up in rubbish bins

Pvc free

Yes
Show all specifications

Documents & downloads

hide show
Filter items
  • All

  • CAD Files and Packs

  • Technical Data Catalogues

  • Data Bulletin

  • Environmental Disclosure

  • End of Life Manual

  • Installation Instruction

  • Certificates (MSDS)

  • Declaration of Conformity