TeSys D, Contactor, TeSys Deca, 3P(3 NO), AC-3/AC-3e, 0 to 440V, 25A, 48-130VAC/DC coil

TeSys D, Contactor, TeSys Deca, 3P(3 NO), AC-3/AC-3e, 0 to 440V, 25A, 48-130VAC/DC coil

Item Number: LC1D25EHE

Datasheet

Product Dimensions

Width icon

Width45 mm

Height icon

Height85 mm

Depth icon

Depth92 mm

Barcode

Qty UoM EAN Colour
-
-
-

Specifications

Design

Range

TeSys|TeSys Deca

Range of product

TeSys Deca

Product or component type

contactor

Sustainable offer status

Green Premium product

Warranty

18 months

Physical

[ue] rated operational voltage

power circuit: <= 690 V AC 25...400 Hz

[ie] rated operational current

25 A (at <60 °C) at <= 440 V AC-3 for power circuit|40 A (at <60 °C) at <= 440 V AC-1 for power circuit|25 A (at <60 °C) at <= 440 V AC-3e for power circuit

Mechanical durability

15 Mcycles

Electrical durability

2 Mcycles 21 A AC-3 at Ue <= 440 V|0.9 Mcycles 40 A AC-1 at Ue <= 440 V|2 Mcycles 21 A AC-3e at Ue <= 440 V

Connections - terminals

control circuit: screw clamp terminals 1 1-4 mm² - cable stiffness: flexible without cable end|control circuit: screw clamp terminals 2 1-4 mm² - cable stiffness: flexible without cable end|control circuit: screw clamp terminals 1 1-4 mm² - cable stiffness: flexible with cable end|control circuit: screw clamp terminals 2 1-2.5 mm² - cable stiffness: flexible with cable end|control circuit: screw clamp terminals 1 1-4 mm² - cable stiffness: solid|control circuit: screw clamp terminals 2 1-4 mm² - cable stiffness: solid|power circuit: screw clamp terminals 1 2.5-10 mm² - cable stiffness: flexible without cable end|power circuit: screw clamp terminals 2 2.5-10 mm² - cable stiffness: flexible without cable end|power circuit: screw clamp terminals 1 1-10 mm² - cable stiffness: flexible with cable end|power circuit: screw clamp terminals 2 1.5-6 mm² - cable stiffness: flexible with cable end|power circuit: screw clamp terminals 1 1.5-10 mm² - cable stiffness: solid|power circuit: screw clamp terminals 2 2.5-10 mm² - cable stiffness: solid

Insulation resistance

> 10 MOhm for signalling circuit

Mounting support

plate|rail

Standards

EN/IEC 60947-4-1|EN/IEC 60947-5-1|UL 60947-4-1|CSA C22.2 No 60947-4-1|IEC 60335-1

Product certifications

CCC|CSA|EAC|UL|KC|DNV-GL|LROS (Lloyds register of shipping)|UKCA

Ip degree of protection

IP20 front face conforming to IEC 60529

Climatic withstand

conforming to IACS E10 exposure to damp heat| conforming to IEC 60947-1 Annex Q category D exposure to damp heat

Height

85 mm

Width

45 mm

Depth

92 mm

Net weight

0.433 kg

Reach regulation

Reference contains Substances of Very High Concern above the threshold

Eu rohs directive

Compliant with Exemptions

Mercury free

Yes

Rohs exemption information

Yes

China rohs regulation

Product out of China RoHS scope. Substance declaration for your information

Environmental disclosure

ENVPEP1609001EN

Circularity profile

ENVEOLI1609001EN

Others

Package 1 bare product quantity

1

Device short name

LC1D

Contactor application

motor control|resistive load

Utilisation category

AC-3|AC-1|AC-3e

Poles description

3P

[uc] control circuit voltage

48...130 V AC 50/60 Hz|48...130 V DC

Motor power kw

5.5 kW at 220...230 V AC 50 Hz (AC-3)|11 kW at 380...400 V AC 50 Hz (AC-3)|11 kW at 415 V AC 50 Hz (AC-3)|11 kW at 440 V AC 50 Hz (AC-3)|15 kW at 500 V AC 50 Hz (AC-3)|15 kW at 660...690 V AC 50 Hz (AC-3)|5.5 kW at 220...230 V AC 50 Hz (AC-3e)|11 kW at 380...400 V AC 50 Hz (AC-3e)|11 kW at 415 V AC 50 Hz (AC-3e)|11 kW at 440 V AC 50 Hz (AC-3e)|15 kW at 500 V AC 50 Hz (AC-3e)|15 kW at 660...690 V AC 50 Hz (AC-3e)

Motor power hp

2 hp at 115 V AC 60 Hz for 1 phase motors|3 hp at 230/240 V AC 60 Hz for 1 phase motors|7.5 hp at 200/208 V AC 60 Hz for 3 phases motors|7.5 hp at 230/240 V AC 60 Hz for 3 phases motors|15 hp at 460/480 V AC 60 Hz for 3 phases motors|20 hp at 575/600 V AC 60 Hz for 3 phases motors

Compatibility code

LC1D

Pole contact composition

3 NO

Protective cover

with

[ith] conventional free air thermal current

10 A (at 60 °C) for signalling circuit|40 A (at 60 °C) for power circuit

Irms rated making capacity

140 A AC for signalling circuit conforming to IEC 60947-5-1|250 A DC for signalling circuit conforming to IEC 60947-5-1|450 A at 440 V for power circuit conforming to IEC 60947

Rated breaking capacity

450 A at 440 V for power circuit conforming to IEC 60947

[icw] rated short-time withstand current

100 A - 1 s for signalling circuit|120 A - 500 ms for signalling circuit|140 A - 100 ms for signalling circuit|50 A 40 °C - 10 min for power circuit|120 A 40 °C - 1 min for power circuit|240 A 40 °C - 10 s for power circuit|380 A 40 °C - 1 s for power circuit

Associated fuse rating

10 A gG for signalling circuit conforming to IEC 60947-5-1|63 A gG at <= 690 V coordination type 1 for power circuit|40 A gG at <= 690 V coordination type 2 for power circuit

Average impedance

2 mOhm - Ith 40 A 50 Hz for power circuit

Power dissipation per pole

3.2 W AC-1|1.25 W AC-3|1.25 W AC-3e

[ui] rated insulation voltage

power circuit: 690 V conforming to IEC 60947-4-1|signalling circuit: 690 V conforming to IEC 60947-1

Overvoltage category

III

Pollution degree

3

[uimp] rated impulse withstand voltage

6 kV conforming to IEC 60947

Safety reliability level

B10d = 1369863 cycles contactor with nominal load conforming to EN/ISO 13849-1|B10d = 20000000 cycles contactor with mechanical load conforming to EN/ISO 13849-1

Control circuit type

AC/DC at 50/60 Hz AC/DC electronic

Coil technology

built-in bidirectional peak limiting

Control circuit voltage limits

<= 0.1 Uc (-40-70 °C):drop-out AC/DC|0.85...1.1 Uc (-40-60 °C):operational AC/DC|1...1.1 Uc (60-70 °C):operational AC/DC

Inrush power in va

25 VA 50/60 Hz (at 20 °C)

Inrush power in w

24 W (at 20 °C)

Hold-in power consumption in va

1.3...1.3 VA 50/60 Hz (at 20 °C)

Hold-in power consumption in w

0.8...0.8 W at 20 °C

Heat dissipation

0.8...0.8 W at 50/60 Hz

Operating time

45...55 ms closing|20...90 ms opening

Maximum operating rate

3600 cyc/h 60 °C

Tightening torque

control circuit: 1.7 N.m - on screw clamp terminals - with screwdriver flat Ø 6 mm|control circuit: 1.7 N.m - on screw clamp terminals - with screwdriver Philips No 2|power circuit: 2.5 N.m - on screw clamp terminals - with screwdriver flat Ø 6 mm|power circuit: 2.5 N.m - on screw clamp terminals - with screwdriver Philips No 2|power circuit: 2.5 N.m - on screw clamp terminals - with screwdriver pozidriv No 2 M4|control circuit: 1.7 N.m - on screw clamp terminals - with screwdriver pozidriv No 2 M3.5

Auxiliary contact composition

1 NO + 1 NC

Auxiliary contacts type

type mechanically linked 1 NO + 1 NC conforming to IEC 60947-5-1| type mirror contact 1 NC conforming to IEC 60947-4-1

Signalling circuit frequency

25...400 Hz

Minimum switching voltage

17 V for signalling circuit

Minimum switching current

5 mA for signalling circuit

Non-overlap time

1.5 ms on de-energisation between NC and NO contact|1.5 ms on energisation between NC and NO contact

Permissible ambient air temperature around the device

-40...60 °C|60...70 °C with derating

Operating altitude

0...3000 m

Fire resistance

850 °C conforming to IEC 60695-2-1

Flame retardance

V1 conforming to UL 94

Mechanical robustness

vibrations contactor open (2 Gn, 5...300 Hz) |vibrations contactor closed (4 Gn, 5...300 Hz) |shocks contactor closed (15 Gn for 11 ms) |shocks contactor open (8 Gn for 11 ms)

Unit type of package 1

PCE

Number of units in package 1

1

Package 1 height

5.5 cm

Package 1 width

9.5 cm

Package 1 length

11.8 cm

Package 1 weight

456.0 g

Unit type of package 2

S02

Number of units in package 2

15

Package 2 height

15.0 cm

Package 2 width

30.0 cm

Package 2 length

40.0 cm

Package 2 weight

7.208 kg

Weee

The product must be disposed on European Union markets following specific waste collection and never end up in rubbish bins

Halogen content performance

Halogen free plastic parts & cables product
Show all specifications

Documents & downloads

hide show
Filter items
  • All

  • Product Brochures

  • CAD Files and Packs

  • Technical Data Catalogues

  • Installation Instruction

  • Data Bulletin

  • Environmental Disclosure

  • End of Life Manual

  • Certificates (MSDS)

  • Declaration of Conformity