TeSys D, Contactor Coil, LX1D8, 48 V AC 50/60 Hz for 115 & 150 A Contactor

TeSys D, Contactor Coil, LX1D8, 48 V AC 50/60 Hz for 115 & 150 A Contactor

Item Number: LX1D8E7

TeSys Deca replacement AC coil 48V 50/60Hz for TeSys Deca contactors. To be used with 3 and 4-pole contactors LC1 D115, D150. It operates in the voltage limits 0.8-1.15 Uc and environments until 55°C Coil with integral suppression device fitted as standard. Green Premium compliant (RoHS/REACh).

Datasheet

Barcode

Qty UoM EAN Colour
-
-
-

Specifications

Design

Range of product

TeSys Deca

Range

TeSys

Product or component type

contactor coil

Product compatibility

LC1D150|LC1D115

Sustainable offer status

Green Premium product

Warranty

18 months

Physical

Mechanical durability

8 Mcycles

Ambient air temperature for operation

-5...60 °C

Reach regulation

Reference contains Substances of Very High Concern above the threshold

Reach free of svhc

Yes

Eu rohs directive

Pro-active compliance (Product out of EU RoHS legal scope)

Mercury free

Yes

Rohs exemption information

Yes

China rohs regulation

Product out of China RoHS scope. Substance declaration for your information

Environmental disclosure

ENVPEP110205EN

Circularity profile

N/A

California proposition 65

WARNING: This product can expose you to chemicals including: Antimony oxide & Antimony trioxide, which is known to the State of California to cause cancer. For more information go to www.P65Warnings.ca.gov

Others

Package 1 bare product quantity

1

Device short name

LX1D8

Control circuit type

AC at 50/60 Hz

[uc] control circuit voltage

48 V AC 50/60 Hz

Average resistance

1061 Ohm at 20 °C

Inductance of closed circuit

24.19 H

Maximum operating rate

1200 cyc/h 60 °C

Coil technology

without built-in suppressor module

Control circuit voltage limits

drop-out: 0.3...0.5 Uc at 50/60 Hz (at <55 °C)|operational: 0.8...1.15 Uc at 50/60 Hz (at <55 °C)

Inrush power in va

280...350 VA 60 Hz cos phi 0.9 (at 20 °C)|280...350 VA 50 Hz cos phi 0.9 (at 20 °C)

Hold-in power consumption in va

2...18 VA 60 Hz cos phi 0.9 (at 20 °C)|2...18 VA 50 Hz cos phi 0.9 (at 20 °C)

Heat dissipation

3...4.5 W at 50/60 Hz

Unit type of package 1

PCE

Number of units in package 1

1

Package 1 height

6.2 cm

Package 1 width

11.5 cm

Package 1 length

17.0 cm

Package 1 weight

296.0 g

Unit type of package 2

S03

Number of units in package 2

20

Package 2 height

30.0 cm

Package 2 width

30.0 cm

Package 2 length

40.0 cm

Package 2 weight

6.633 kg