TeSys D, Contactor, 4P(2NO+2NC),AC-1 <=440V 80 A 240V AC 50/60Hz coil

TeSys D, Contactor, 4P(2NO+2NC),AC-1 <=440V 80 A 240V AC 50/60Hz coil

Item Number: LC1D65008U7

Datasheet

Product Dimensions

Width icon

Width85 mm

Height icon

Height127 mm

Depth icon

Depth125 mm

Barcode

Qty UoM EAN Colour
-
-
-

Specifications

Design

Range

TeSys

Range of product

TeSys Deca

Product or component type

contactor

Sustainable offer status

Green Premium product

Warranty

18 months

Physical

[ue] rated operational voltage

power circuit: <= 690 V AC 25...400 Hz|power circuit: <= 300 V DC

[ie] rated operational current

80 A (at <60 °C) at <= 440 V AC AC-1 for power circuit

Mechanical durability

6 Mcycles

Electrical durability

1.4 Mcycles 80 A AC-1 at Ue <= 440 V

Connections - terminals

control circuit: screw clamp terminals 2 1-2.5 mm² - cable stiffness: flexible with cable end|control circuit: screw clamp terminals 1 1-4 mm² - cable stiffness: flexible without cable end|control circuit: screw clamp terminals 2 1-4 mm² - cable stiffness: flexible without cable end|control circuit: screw clamp terminals 1 1-4 mm² - cable stiffness: flexible with cable end|control circuit: screw clamp terminals 1 1-4 mm² - cable stiffness: solid without cable end|control circuit: screw clamp terminals 2 1-4 mm² - cable stiffness: solid without cable end|power circuit: screw clamp terminals 1 1-35 mm² - cable stiffness: flexible without cable end|power circuit: screw clamp terminals 2 1-25 mm² - cable stiffness: flexible without cable end|power circuit: screw clamp terminals 1 1-35 mm² - cable stiffness: flexible with cable end|power circuit: screw clamp terminals 2 1-25 mm² - cable stiffness: flexible with cable end|power circuit: screw clamp terminals 1 1-35 mm² - cable stiffness: solid without cable end|power circuit: screw clamp terminals 2 1-25 mm² - cable stiffness: solid without cable end

Mounting support

rail|plate

Standards

CSA C22.2 No 14|EN 60947-4-1|EN 60947-5-1|IEC 60947-4-1|IEC 60947-5-1|UL 508

Product certifications

CCC|GOST|RINA|DNV|BV|LROS (Lloyds register of shipping)|CSA|UL|GL

Ip degree of protection

IP20 front face conforming to IEC 60529

Climatic withstand

conforming to IACS E10 exposure to damp heat

Height

127 mm

Width

85 mm

Depth

125 mm

Net weight

1.45 kg

Reach regulation

Free of Substances of Very High Concern above the threshold

Reach free of svhc

Yes

Eu rohs directive

Compliant

Toxic heavy metal free

Yes

Mercury free

Yes

China rohs regulation

 Pro-active China RoHS declaration (out of China RoHS legal scope)

Rohs exemption information

Yes

Environmental disclosure

ENVPEP110205EN

Circularity profile

N/A

California proposition 65

WARNING: This product can expose you to chemicals including: Antimony oxide & Antimony trioxide, which is known to the State of California to cause cancer. For more information go to www.P65Warnings.ca.gov

Others

Package 1 bare product quantity

1

Device short name

LC1D

Contactor application

resistive load

Utilisation category

AC-1

Poles description

4P

[uc] control circuit voltage

240 V AC 50/60 Hz

Compatibility code

LC1D

Pole contact composition

2 NO + 2 NC

Protective cover

without

[ith] conventional free air thermal current

80 A (at 60 °C) for power circuit

Irms rated making capacity

1000 A at 440 V for power circuit conforming to IEC 60947

Rated breaking capacity

1000 A at 440 V for power circuit conforming to IEC 60947

[icw] rated short-time withstand current

640 A 40 °C - 10 s for power circuit|900 A 40 °C - 1 s for power circuit|110 A 40 °C - 10 min for power circuit|260 A 40 °C - 1 min for power circuit

Associated fuse rating

125 A gG at <= 690 V coordination type 1 for power circuit|125 A gG at <= 690 V coordination type 2 for power circuit

Average impedance

1.5 mOhm - Ith 80 A 50 Hz for power circuit

Power dissipation per pole

9.6 W AC-1

[ui] rated insulation voltage

power circuit: 600 V CSA certified|power circuit: 600 V UL certified|power circuit: 690 V conforming to IEC 60947-4-1

Overvoltage category

III

Pollution degree

3

[uimp] rated impulse withstand voltage

6 kV conforming to IEC 60947

Safety reliability level

B10d = 1369863 cycles contactor with nominal load conforming to EN/ISO 13849-1|B10d = 20000000 cycles contactor with mechanical load conforming to EN/ISO 13849-1

Control circuit type

AC at 50/60 Hz

Coil technology

without built-in suppressor module

Control circuit voltage limits

0.3...0.6 Uc (-40-70 °C):drop-out AC 50/60 Hz|0.8...1.1 Uc (-40-60 °C):operational AC 50 Hz|0.85...1.1 Uc (-40-60 °C):operational AC 60 Hz|1...1.1 Uc (60-70 °C):operational AC 50/60 Hz

Inrush power in va

140 VA 60 Hz cos phi 0.75 (at 20 °C)|160 VA 50 Hz cos phi 0.75 (at 20 °C)

Hold-in power consumption in va

13 VA 60 Hz cos phi 0.3 (at 20 °C)|15 VA 50 Hz cos phi 0.3 (at 20 °C)

Heat dissipation

4...5 W at 50/60 Hz

Operating time

4...19 ms opening|12...26 ms closing

Maximum operating rate

3600 cyc/h 60 °C

Tightening torque

control circuit: 1.7 N.m - on screw clamp terminals - with screwdriver flat Ø 6 mm|control circuit: 1.7 N.m - on screw clamp terminals - with screwdriver Philips No 2|power circuit: 8 N.m - on screw clamp terminals - cable 25-35 mm² hexagonal screw head 4 mm|power circuit: 5 N.m - on screw clamp terminals - cable 1-25 mm² hexagonal screw head 4 mm

Contact compatibility

M1

Protective treatment

TH conforming to IEC 60068-2-30

Permissible ambient air temperature around the device

-40...60 °C|60...70 °C with derating

Operating altitude

0...3000 m

Fire resistance

850 °C conforming to IEC 60695-2-1

Flame retardance

V1 conforming to UL 94

Mechanical robustness

shocks contactor open (8 Gn for 11 ms) |shocks contactor closed (10 Gn for 11 ms) |vibrations contactor opened (2 Gn, 5...300 Hz) |vibrations contactor closed (3 Gn, 5...300 Hz)

Unit type of package 1

PCE

Number of units in package 1

1

Package 1 height

9.1 cm

Package 1 width

12.6 cm

Package 1 length

13.2 cm

Package 1 weight

1.5 kg

Weee

The product must be disposed on European Union markets following specific waste collection and never end up in rubbish bins

Pvc free

Yes
Show all specifications

Documents & downloads

hide show
Filter items
  • All

  • CAD Files and Packs

  • Technical Data Catalogues

  • Installation Instruction

  • Environmental Disclosure

  • Data Bulletin

  • Certificates (MSDS)