TeSys D, Contactor, 3P(3 NO), AC-3/AC-3e, 0 to 440V, 9A, 220VAC 50/60Hz coil

TeSys D, Contactor, 3P(3 NO), AC-3/AC-3e, 0 to 440V, 9A, 220VAC 50/60Hz coil

Item Number: LC1D09M7

Datasheet

Product Dimensions

Width icon

Width45 mm

Height icon

Height77 mm

Depth icon

Depth86 mm

Barcode

Qty UoM EAN Colour
-
-
-

Specifications

Design

Range of product

TeSys Deca

Product or component type

contactor

Sustainable offer status

Green Premium product

Warranty

18 months

Physical

[ue] rated operational voltage

power circuit: <= 690 V AC 25...400 Hz|power circuit: <= 300 V DC

[ie] rated operational current

9 A (at <60 °C) at <= 440 V AC AC-3 for power circuit|25 A (at <60 °C) at <= 440 V AC AC-1 for power circuit|9 A (at <60 °C) at <= 440 V AC AC-3e for power circuit

Mechanical durability

15 Mcycles

Electrical durability

0.6 Mcycles 25 A AC-1 at Ue <= 440 V|2 Mcycles 9 A AC-3 at Ue <= 440 V|2 Mcycles 9 A AC-3e at Ue <= 440 V

Connections - terminals

power circuit: screw clamp terminals 1 1-4 mm² - cable stiffness: flexible without cable end|power circuit: screw clamp terminals 2 1-4 mm² - cable stiffness: flexible without cable end|power circuit: screw clamp terminals 1 1-4 mm² - cable stiffness: flexible with cable end|power circuit: screw clamp terminals 2 1-2.5 mm² - cable stiffness: flexible with cable end|power circuit: screw clamp terminals 1 1-4 mm² - cable stiffness: solid without cable end|power circuit: screw clamp terminals 2 1-4 mm² - cable stiffness: solid without cable end|control circuit: screw clamp terminals 1 1-4 mm² - cable stiffness: flexible without cable end|control circuit: screw clamp terminals 2 1-4 mm² - cable stiffness: flexible without cable end|control circuit: screw clamp terminals 1 1-4 mm² - cable stiffness: flexible with cable end|control circuit: screw clamp terminals 2 1-2.5 mm² - cable stiffness: flexible with cable end|control circuit: screw clamp terminals 1 1-4 mm² - cable stiffness: solid without cable end|control circuit: screw clamp terminals 2 1-4 mm² - cable stiffness: solid without cable end

Insulation resistance

> 10 MOhm for signalling circuit

Mounting support

plate|rail

Standards

CSA C22.2 No 14|EN 60947-4-1|EN 60947-5-1|IEC 60947-4-1|IEC 60947-5-1|UL 60947-4-1|IEC 60335-1:Clause 30.2|IEC 60335-2-40:Annex JJ|UL 60335-2-40:Annex JJ|CSA C22.2 No 60947-4-1

Product certifications

UL|CCC|CSA|Marine|UKCA|EAC|CB Scheme

Ip degree of protection

IP20 front face conforming to IEC 60529

Climatic withstand

conforming to IACS E10 exposure to damp heat| conforming to IEC 60947-1 Annex Q category D exposure to damp heat

Height

77 mm

Width

45 mm

Depth

86 mm

Net weight

0.32 kg

Reach regulation

Reference contains Substances of Very High Concern above the threshold

Eu rohs directive

Compliant

Toxic heavy metal free

Yes

Mercury free

Yes

Rohs exemption information

Yes

China rohs regulation

 Pro-active China RoHS declaration (out of China RoHS legal scope)

Environmental disclosure

ENVPEP1501004

Circularity profile

ENVEOLI1501004

California proposition 65

WARNING: This product can expose you to chemicals including: Antimony oxide & Antimony trioxide, which is known to the State of California to cause cancer. For more information go to www.P65Warnings.ca.gov

Others

Life cycle assessment data

Yes

Substance regulation data deliverable

Yes

Package 1 bare product quantity

1

Package 2 bare product quantity

20

Package 3 bare product quantity

320

Device short name

LC1D

Contactor application

motor control|resistive load

Utilisation category

AC-4|AC-3|AC-1|AC-3e

Poles description

3P

[uc] control circuit voltage

220 V AC 50/60 Hz

Motor power kw

2.2 kW at 220...230 V AC 50/60 Hz (AC-3)|4 kW at 380...400 V AC 50/60 Hz (AC-3)|4 kW at 415...440 V AC 50/60 Hz (AC-3)|5.5 kW at 500 V AC 50/60 Hz (AC-3)|5.5 kW at 660...690 V AC 50/60 Hz (AC-3)|2.2 kW at 400 V AC 50/60 Hz (AC-4)|2.2 kW at 220...230 V AC 50/60 Hz (AC-3e)|4 kW at 380...400 V AC 50/60 Hz (AC-3e)|4 kW at 415...440 V AC 50/60 Hz (AC-3e)|5.5 kW at 500 V AC 50/60 Hz (AC-3e)|5.5 kW at 660...690 V AC 50/60 Hz (AC-3e)

Motor power hp

1 hp at 230/240 V AC 50/60 Hz for 1 phase motors|2 hp at 200/208 V AC 50/60 Hz for 3 phases motors|2 hp at 230/240 V AC 50/60 Hz for 3 phases motors|5 hp at 460/480 V AC 50/60 Hz for 3 phases motors|7.5 hp at 575/600 V AC 50/60 Hz for 3 phases motors|0.33 hp at 115 V AC 50/60 Hz for 1 phase motors

Compatibility code

LC1D

Pole contact composition

3 NO

Protective cover

with

[ith] conventional free air thermal current

25 A (at 60 °C) for power circuit|10 A (at 60 °C) for signalling circuit

Irms rated making capacity

250 A at 440 V for power circuit conforming to IEC 60947|140 A AC for signalling circuit conforming to IEC 60947-5-1|250 A DC for signalling circuit conforming to IEC 60947-5-1

Rated breaking capacity

250 A at 440 V for power circuit conforming to IEC 60947

[icw] rated short-time withstand current

105 A 40 °C - 10 s for power circuit|210 A 40 °C - 1 s for power circuit|30 A 40 °C - 10 min for power circuit|61 A 40 °C - 1 min for power circuit|100 A - 1 s for signalling circuit|120 A - 500 ms for signalling circuit|140 A - 100 ms for signalling circuit

Associated fuse rating

10 A gG for signalling circuit conforming to IEC 60947-5-1|25 A gG at <= 690 V coordination type 1 for power circuit|20 A gG at <= 690 V coordination type 2 for power circuit

Average impedance

2.5 mOhm - Ith 25 A 50 Hz for power circuit

Power dissipation per pole

1.56 W AC-1|0.2 W AC-3|0.2 W AC-3e

[ui] rated insulation voltage

power circuit: 690 V conforming to IEC 60947-4-1|power circuit: 600 V CSA certified|power circuit: 600 V UL certified|signalling circuit: 690 V conforming to IEC 60947-1|signalling circuit: 600 V CSA certified|signalling circuit: 600 V UL certified

Overvoltage category

III

Pollution degree

3

[uimp] rated impulse withstand voltage

6 kV conforming to IEC 60947

Safety reliability level

B10d = 1369863 cycles contactor with nominal load conforming to EN/ISO 13849-1|B10d = 20000000 cycles contactor with mechanical load conforming to EN/ISO 13849-1

Control circuit type

AC at 50/60 Hz standard

Coil technology

without built-in suppressor module

Control circuit voltage limits

0.3...0.6 Uc (-40-70 °C):drop-out AC 50/60 Hz|0.8...1.1 Uc (-40-60 °C):operational AC 50 Hz|0.85...1.1 Uc (-40-60 °C):operational AC 60 Hz|1...1.1 Uc (60-70 °C):operational AC 50/60 Hz

Inrush power in va

70 VA 60 Hz cos phi 0.75 (at 20 °C)|70 VA 50 Hz cos phi 0.75 (at 20 °C)

Hold-in power consumption in va

7.5...7.5 VA 60 Hz cos phi 0.3 (at 20 °C)|7 VA 50 Hz cos phi 0.3 (at 20 °C)

Heat dissipation

2...3 W at 50/60 Hz

Operating time

12...22 ms closing|4...19 ms opening

Maximum operating rate

3600 cyc/h 60 °C

Maximum operating rate

3600 cyc/h at 60 °C

Tightening torque

power circuit: 1.7 N.m - on screw clamp terminals - with screwdriver flat Ø 6 mm|power circuit: 1.7 N.m - on screw clamp terminals - with screwdriver Philips No 2|control circuit: 1.7 N.m - on screw clamp terminals - with screwdriver flat Ø 6 mm|control circuit: 1.7 N.m - on screw clamp terminals - with screwdriver Philips No 2|control circuit: 1.7 N.m - on screw clamp terminals - with screwdriver pozidriv No 2|power circuit: 1.7 N.m - on screw clamp terminals - with screwdriver pozidriv No 2

Auxiliary contact composition

1 NO + 1 NC

Auxiliary contacts type

type mechanically linked 1 NO + 1 NC conforming to IEC 60947-5-1| type mirror contact 1 NC conforming to IEC 60947-4-1

Signalling circuit frequency

25...400 Hz

Minimum switching voltage

17 V for signalling circuit

Minimum switching current

5 mA for signalling circuit

Non-overlap time

1.5 ms on de-energisation between NC and NO contact|1.5 ms on energisation between NC and NO contact

Contact compatibility

M2

Protective treatment

TH conforming to IEC 60068-2-30

Permissible ambient air temperature around the device

-40...60 °C|60...70 °C with derating

Operating altitude

0...3000 m

Fire resistance

850 °C conforming to IEC 60695-2-1

Flame retardance

V1 conforming to UL 94

Mechanical robustness

vibrations contactor open (2 Gn, 5...300 Hz) |vibrations contactor closed (4 Gn, 5...300 Hz) |shocks contactor open (10 Gn for 11 ms) |shocks contactor closed (15 Gn for 11 ms)

Unit type of package 1

PCE

Number of units in package 1

1

Package 1 height

5.000 cm

Package 1 width

9.200 cm

Package 1 length

11.500 cm

Package 1 weight

350.000 g

Unit type of package 2

S02

Number of units in package 2

20

Package 2 height

15.000 cm

Package 2 width

30.000 cm

Package 2 length

40.000 cm

Package 2 weight

7.282 kg

Unit type of package 3

P06

Number of units in package 3

320

Package 3 height

75.000 cm

Package 3 width

60.000 cm

Package 3 length

80.000 cm

Package 3 weight

123.500 kg

Sustainable packaging

Yes

Weee

The product must be disposed on European Union markets following specific waste collection and never end up in rubbish bins

Pvc free

Yes
Show all specifications

Documents & downloads

hide show
Filter items
  • All

  • CAD Files and Packs

  • Technical Data Catalogues

  • Installation Instruction

  • Data Bulletin

  • Environmental Disclosure

  • End of Life Manual

  • Technical Drawing

  • Certificates (MSDS)

  • Declaration of Conformity

  • eTechPub

Frequently Asked Questions

hide show

What is the coil tolerance for Tesys D-line contactors LC1D09 - LC1D38?

Issue:
LC1D09 - LC1D38 Coil tolerance

Product Line:
Contactors and Starters, IEC

Environment:
Tesys D Contactors

Cause:
Needs the coil tolerance for Tesys D-line contactors LC1D09 - LC1D38.

Resolution:
AC single frequency coils: 50Hz and 60 Hz (-20% / +10%);
AC dual frequency coils: 50Hz (-20% / +10%) ; 60Hz (-15% / +10%)
DC standard coil for LC1D09 -D38 and LC1DT20 to DT40: (-30% / +25%)
DC standard coil for LP1D12 and D25: (-20% / +10%)
DC wide range coil for LP1D12 and D25 : (-30% to +25%)

What is the maximum UL/CSA AC voltage rating of the LC1D power contacts ?

Issue:
Identifying maximum voltage of an LC1D contactor

Product Line:
TeSys D Contactors

Environment:
Contactors and Starters IEC

Resolution:
IThe maximum voltage per UL and CSA is 600VAC. 
 

What is the altitude derating for a TeSys D-Line contactor?

Issue:​
What is the altitude derating for a TeSys D-Line contactor?

Product Line:
Digest 177 Section 18 : Contactors and Starters, IEC

Environment:
North American Products

Resolution:
The contactors are fully rated up to 3000 meters. Following are derating multipliers for altitudes above 3000 meters for both voltage and current:

Voltage
3500m x 0.90
4000m x 0.80
4500m x 0.70
5000m x 0.60

Current
3500m x 0.92
4000m x 0.90
4500m x 0.88
5000m x 0.86

For example, an LC1D80 at 5000 meters:
- The maximum rated operational voltage is 1,000V (IEC947-4) and 690V (UL/CSA). At 5000 meters it becomes 1000V x 0.6 = 600V (IEC947-4) and 690V x 0.6 = 414V (UL/CSA).
- The maximum rated operational AC3 current is 80A. At 5000 meters it becomes 80A x 0.86 = 68A.



 

What is the power terminal lug data for the LC1D09, LC1DT20, LC1D12, and LC1DT25 contactor?

Issue:
Power terminal lug data required for the 9 and 12 amp rated Tesys D contactors

Product Line:
IEC Contactors and Starters

Environment:
Tesys D Contactors

Resolution:
For contactors with screw clamp terminals:
stranded cable w/o cable end : One or Two #18-10 AWG per terminal.
stranded cable w/cable end: One or Two #18-10 AWG per terminal.
solid cable: One or Two #18-8 AWG per terminal.