TeSys D, Contactor, 3P(3 NO), AC-3/AC-3e, 0 to 440V, 25A, 24VDC coil

TeSys D Contactor

Item Number: LC1D25BD

Contact your Wholesaler for pricing

Datasheet

PDF datasheet

For LC1D25BD

Product Dimensions

Width icon

Width45 mm

Height icon

Height85 mm

Depth icon

Depth101 mm

Barcode

Qty UoM EAN Colour
1 3389110355994 -

Specifications

Design

Range of product

TeSys Deca

Product or component type

contactor

Warranty

18 months

Physical

[ue] rated operational voltage

  • power circuit: <= 690 V AC 25...400 Hz
  • power circuit: <= 300 V DC

[ie] rated operational current

  • 25 A (at <60 °C) at <= 440 V AC AC-3 for power circuit
  • 40 A (at <60 °C) at <= 440 V AC AC-1 for power circuit
  • 25 A (at <60 °C) at <= 440 V AC AC-3e for power circuit

Mechanical durability

30 Mcycles

Electrical durability

  • 1.65 Mcycles 25 A AC-3 at Ue <= 440 V
  • 1.4 Mcycles 40 A AC-1 at Ue <= 440 V
  • 1.65 Mcycles 25 A AC-3e at Ue <= 440 V

Connections - terminals

  • control circuit: screw clamp terminals 1 1-4 mm² - cable stiffness: flexible without cable end
  • control circuit: screw clamp terminals 2 1-4 mm² - cable stiffness: flexible without cable end
  • control circuit: screw clamp terminals 1 1-4 mm² - cable stiffness: flexible with cable end
  • control circuit: screw clamp terminals 2 1-2.5 mm² - cable stiffness: flexible with cable end
  • control circuit: screw clamp terminals 1 1-4 mm² - cable stiffness: solid without cable end
  • control circuit: screw clamp terminals 2 1-4 mm² - cable stiffness: solid without cable end
  • power circuit: screw clamp terminals 1 2.5-10 mm² - cable stiffness: flexible without cable end
  • power circuit: screw clamp terminals 2 2.5-10 mm² - cable stiffness: flexible without cable end
  • power circuit: screw clamp terminals 1 1-10 mm² - cable stiffness: flexible with cable end
  • power circuit: screw clamp terminals 2 1.5-6 mm² - cable stiffness: flexible with cable end
  • power circuit: screw clamp terminals 1 1.5-10 mm² - cable stiffness: solid without cable end
  • power circuit: screw clamp terminals 2 2.5-10 mm² - cable stiffness: solid without cable end

Insulation resistance

> 10 MOhm for signalling circuit

Mounting support

  • plate
  • rail

Standards

  • CSA C22.2 No 14
  • EN 60947-4-1
  • EN 60947-5-1
  • IEC 60947-4-1
  • IEC 60947-5-1
  • UL 60947-4-1
  • IEC 60335-1:Clause 30.2
  • IEC 60335-2-40:Annex JJ
  • UL 60335-2-40:Annex JJ
  • CSA C22.2 No 60947-4-1

Product certifications

  • UL
  • CCC
  • CSA
  • Marine
  • UKCA
  • EAC
  • CB Scheme

Ip degree of protection

IP20 front face conforming to IEC 60529

Climatic withstand

  • conforming to IACS E10 exposure to damp heat
  • conforming to IEC 60947-1 Annex Q category D exposure to damp heat

Height

85 mm

Width

45 mm

Depth

101 mm

Net weight

0.53 kg

Reach regulation

Reference contains Substances of Very High Concern above the threshold

Eu rohs directive

Compliant with Exemptions

Mercury free

Yes

Rohs exemption information

Yes

China rohs regulation

Product out of China RoHS scope. Substance declaration for your information

Environmental disclosure

ENVPEP110230EN

Circularity profile

ENVEOLI1102030EN

California proposition 65

WARNING: This product can expose you to chemicals including: Antimony oxide & Antimony trioxide, which is known to the State of California to cause cancer. For more information go to www.P65Warnings.ca.gov
Show all specifications

Documents & downloads

hide show
Filter items
  • All

  • CAD Files and Packs

  • Technical Data Catalogues

  • Data Bulletin

  • End of Life Manual

  • Environmental Disclosure

  • Installation Instruction

  • Technical illustration

  • Technical Drawing

  • Certificates (MSDS)

  • Declaration of Conformity

  • eTechPub

  • Page 2  /  5
  • Page 3  /  5
  • Page 4  /  5
  • Page 5  /  5

Frequently Asked Questions

hide show

What is the difference between the LAD4TB and LAD4TBDL bi-directional peak limiting diode?

Issue:
Identifying the difference between LAD4TB and LAD4TBDL

Product Line:
IEC contactors and starters

Environment:
Products sold and used in the United States

Cause:
Identifying the difference between two similar part numbers

Resolution:
The LAD4TB is for 24V AC coils for the Tesys Series LC1D09 through LC1D38 contactors when supplied with G7 voltage code. The LAD4TBDL is 24 vdc bi-directional diode offered as a replacement if for some reason the diode supplied with the Tesys LC1D09 through LC1D38 contactors when ordered with BD or BL voltage code breaks or is no longer working.


 

Where do I find the Coil voltage on the Tesys D 3 Pole AC Contactor?

On the Tesys D 3 Pole AC Contactor you will find the coil voltage marked at the top, behind the Power terminals of the Contactor, for example U7, 240V 50/60 Hz

For the DC Version, the coil voltage is marked on the front of the Contactor. Hence it has got complete part number for the Contactor on the front, for example: LC1D25BD for 24V DC Coil.