TeSys D, Contactor, 3P(3 NO), AC-3/AC-3e, 0 to 440V, 18A, 220VAC 50/60Hz coil
Item Number: LC1D18M7
Specifications
Design
Range of product
Product or component type
Warranty
Physical
[ue] rated operational voltage
- power circuit: <= 690 V AC 25...400 Hz
- power circuit: <= 300 V DC
[ie] rated operational current
- 18 A (at <60 °C) at <= 440 V AC AC-3 for power circuit
- 32 A (at <60 °C) at <= 440 V AC AC-1 for power circuit
- 18 A (at <60 °C) at <= 440 V AC AC-3e for power circuit
Mechanical durability
Electrical durability
- 1.65 Mcycles 18 A AC-3 at Ue <= 440 V
- 1 Mcycles 32 A AC-1 at Ue <= 440 V
- 1.65 Mcycles 18 A AC-3e at Ue <= 440 V
Connections - terminals
- control circuit: screw clamp terminals 1 1-4 mm² - cable stiffness: flexible without cable end
- control circuit: screw clamp terminals 2 1-4 mm² - cable stiffness: flexible without cable end
- control circuit: screw clamp terminals 1 1-4 mm² - cable stiffness: flexible with cable end
- control circuit: screw clamp terminals 2 1-2.5 mm² - cable stiffness: flexible with cable end
- control circuit: screw clamp terminals 1 1-4 mm² - cable stiffness: solid without cable end
- control circuit: screw clamp terminals 2 1-4 mm² - cable stiffness: solid without cable end
- power circuit: screw clamp terminals 1 1.5-6 mm² - cable stiffness: flexible without cable end
- power circuit: screw clamp terminals 2 1.5-6 mm² - cable stiffness: flexible without cable end
- power circuit: screw clamp terminals 1 1-6 mm² - cable stiffness: flexible with cable end
- power circuit: screw clamp terminals 2 1-4 mm² - cable stiffness: flexible with cable end
- power circuit: screw clamp terminals 1 1.5-6 mm² - cable stiffness: solid without cable end
- power circuit: screw clamp terminals 2 1.5-6 mm² - cable stiffness: solid without cable end
Insulation resistance
Mounting support
- plate
- rail
Standards
- CSA C22.2 No 14
- EN 60947-4-1
- EN 60947-5-1
- IEC 60947-4-1
- IEC 60947-5-1
- UL 60947-4-1
- IEC 60335-1:Clause 30.2
- IEC 60335-2-40:Annex JJ
- UL 60335-2-40:Annex JJ
- CSA C22.2 No 60947-4-1
Product certifications
- UL
- CCC
- CSA
- Marine
- UKCA
- EAC
- CB Scheme
Ip degree of protection
Climatic withstand
- conforming to IACS E10 exposure to damp heat
- conforming to IEC 60947-1 Annex Q category D exposure to damp heat
Height
Width
Depth
Net weight
Reach regulation
Reach free of svhc
Eu rohs directive
Toxic heavy metal free
Mercury free
China rohs regulation
Rohs exemption information
Environmental disclosure
Circularity profile
California proposition 65
Others
Life cycle assessment data
Substance regulation data deliverable
Package 1 bare product quantity
Package 2 bare product quantity
Package 3 bare product quantity
Packaging made with recycled cardboard
Packaging without single use plastic
Device short name
Contactor application
- resistive load
- motor control
Utilisation category
- AC-1
- AC-4
- AC-3
- AC-3e
Poles description
[uc] control circuit voltage
Motor power kw
- 4 kW at 220...230 V AC 50/60 Hz (AC-3)
- 7.5 kW at 380...400 V AC 50/60 Hz (AC-3)
- 9 kW at 415...440 V AC 50/60 Hz (AC-3)
- 10 kW at 500 V AC 50/60 Hz (AC-3)
- 10 kW at 660...690 V AC 50/60 Hz (AC-3)
- 4 kW at 400 V AC 50/60 Hz (AC-4)
- 4 kW at 220...230 V AC 50/60 Hz (AC-3e)
- 7.5 kW at 380...400 V AC 50/60 Hz (AC-3e)
- 9 kW at 415...440 V AC 50/60 Hz (AC-3e)
- 10 kW at 500 V AC 50/60 Hz (AC-3e)
- 10 kW at 660...690 V AC 50/60 Hz (AC-3e)
Motor power hp
- 1 hp at 115 V AC 50/60 Hz for 1 phase motors
- 3 hp at 230/240 V AC 50/60 Hz for 1 phase motors
- 5 hp at 200/208 V AC 50/60 Hz for 3 phases motors
- 5 hp at 230/240 V AC 50/60 Hz for 3 phases motors
- 10 hp at 460/480 V AC 50/60 Hz for 3 phases motors
- 15 hp at 575/600 V AC 50/60 Hz for 3 phases motors
Compatibility code
Pole contact composition
Protective cover
[ith] conventional free air thermal current
- 10 A (at 60 °C) for signalling circuit
- 32 A (at 60 °C) for power circuit
Irms rated making capacity
- 140 A AC for signalling circuit conforming to IEC 60947-5-1
- 250 A DC for signalling circuit conforming to IEC 60947-5-1
- 300 A at 440 V for power circuit conforming to IEC 60947
Rated breaking capacity
[icw] rated short-time withstand current
- 145 A 40 °C - 10 s for power circuit
- 240 A 40 °C - 1 s for power circuit
- 40 A 40 °C - 10 min for power circuit
- 84 A 40 °C - 1 min for power circuit
- 100 A - 1 s for signalling circuit
- 120 A - 500 ms for signalling circuit
- 140 A - 100 ms for signalling circuit
Associated fuse rating
- 10 A gG for signalling circuit conforming to IEC 60947-5-1
- 50 A gG at <= 690 V coordination type 1 for power circuit
- 35 A gG at <= 690 V coordination type 2 for power circuit
Average impedance
Power dissipation per pole
- 2.5 W AC-1
- 0.8 W AC-3
- 0.8 W AC-3e
[ui] rated insulation voltage
- power circuit: 690 V conforming to IEC 60947-4-1
- power circuit: 600 V CSA certified
- power circuit: 600 V UL certified
- signalling circuit: 690 V conforming to IEC 60947-1
- signalling circuit: 600 V CSA certified
- signalling circuit: 600 V UL certified
Overvoltage category
Pollution degree
[uimp] rated impulse withstand voltage
Safety reliability level
- B10d = 1369863 cycles contactor with nominal load conforming to EN/ISO 13849-1
- B10d = 20000000 cycles contactor with mechanical load conforming to EN/ISO 13849-1
Control circuit type
Coil technology
Control circuit voltage limits
- 0.3...0.6 Uc (-40-70 °C):drop-out AC 50/60 Hz
- 0.8...1.1 Uc (-40-60 °C):operational AC 50 Hz
- 0.85...1.1 Uc (-40-60 °C):operational AC 60 Hz
- 1...1.1 Uc (60-70 °C):operational AC 50/60 Hz
Inrush power in va
- 70 VA 60 Hz cos phi 0.75 (at 20 °C)
- 70 VA 50 Hz cos phi 0.75 (at 20 °C)
Hold-in power consumption in va
- 7.5...7.5 VA 60 Hz cos phi 0.3 (at 20 °C)
- 7 VA 50 Hz cos phi 0.3 (at 20 °C)
Heat dissipation
Operating time
- 12...22 ms closing
- 4...19 ms opening
Maximum operating rate
Tightening torque
- power circuit: 1.7 N.m - on screw clamp terminals - with screwdriver flat Ø 6 mm
- power circuit: 1.7 N.m - on screw clamp terminals - with screwdriver Philips No 2
- control circuit: 1.7 N.m - on screw clamp terminals - with screwdriver flat Ø 6 mm
- control circuit: 1.7 N.m - on screw clamp terminals - with screwdriver Philips No 2
- control circuit: 1.7 N.m - on screw clamp terminals - with screwdriver pozidriv No 2
- power circuit: 1.7 N.m - on screw clamp terminals - with screwdriver pozidriv No 2
Auxiliary contact composition
Auxiliary contacts type
- type mechanically linked 1 NO + 1 NC conforming to IEC 60947-5-1
- type mirror contact 1 NC conforming to IEC 60947-4-1
Signalling circuit frequency
Minimum switching voltage
Minimum switching current
Non-overlap time
- 1.5 ms on de-energisation between NC and NO contact
- 1.5 ms on energisation between NC and NO contact
Contact compatibility
Protective treatment
Permissible ambient air temperature around the device
- -40...60 °C
- 60...70 °C with derating
Operating altitude
Fire resistance
Flame retardance
Mechanical robustness
- vibrations contactor open (2 Gn, 5...300 Hz)
- vibrations contactor closed (4 Gn, 5...300 Hz)
- shocks contactor open (10 Gn for 11 ms)
- shocks contactor closed (15 Gn for 11 ms)
Unit type of package 1
Number of units in package 1
Package 1 height
Package 1 width
Package 1 length
Package 1 weight
Unit type of package 2
Number of units in package 2
Package 2 height
Package 2 width
Package 2 length
Package 2 weight
Unit type of package 3
Number of units in package 3
Package 3 height
Package 3 width
Package 3 length
Package 3 weight
Green premium status for reporting
Sustainable packaging
Weee
Pvc free
Pvc free
Take-back
Take-back
Product contributes to saved and avoided emissions
Removable battery
Carbon footprint (kg.eq.co2 per cr, total life cycle)
Global warming ; total life cycle
Documents & downloads
hide show-
All
-
CAD Files and Packs
-
Technical Data Catalogues
-
Data Bulletin
-
End of Life Manual
-
Environmental Disclosure
-
Installation Instruction
-
Technical illustration
-
Technical Drawing
-
Certificates (MSDS)
-
Declaration of Conformity
-
eTechPub
Frequently Asked Questions
hide showLC1D09 - LC1D38 Coil tolerance
Product Line:
Contactors and Starters, IEC
Environment:
Tesys D Contactors
Cause:
Needs the coil tolerance for Tesys D-line contactors LC1D09 - LC1D38.
Resolution:
AC single frequency coils: 50Hz and 60 Hz (-20% / +10%);
AC dual frequency coils: 50Hz (-20% / +10%) ; 60Hz (-15% / +10%)
DC standard coil for LC1D09 -D38 and LC1DT20 to DT40: (-30% / +25%)
DC standard coil for LP1D12 and D25: (-20% / +10%)
DC wide range coil for LP1D12 and D25 : (-30% to +25%)
Identifying maximum voltage of an LC1D contactor
Product Line:
TeSys D Contactors
Environment:
Contactors and Starters IEC
Resolution:
IThe maximum voltage per UL and CSA is 600VAC.
What is the altitude derating for a TeSys D-Line contactor?
Product Line:
Digest 177 Section 18 : Contactors and Starters, IEC
Environment:
North American Products
Resolution:
The contactors are fully rated up to 3000 meters. Following are derating multipliers for altitudes above 3000 meters for both voltage and current:
Voltage
3500m x 0.90
4000m x 0.80
4500m x 0.70
5000m x 0.60
Current
3500m x 0.92
4000m x 0.90
4500m x 0.88
5000m x 0.86
For example, an LC1D80 at 5000 meters:
- The maximum rated operational voltage is 1,000V (IEC947-4) and 690V (UL/CSA). At 5000 meters it becomes 1000V x 0.6 = 600V (IEC947-4) and 690V x 0.6 = 414V (UL/CSA).
- The maximum rated operational AC3 current is 80A. At 5000 meters it becomes 80A x 0.86 = 68A.