Harmony Control Relays, Modular temperature Control Relay, 5 A , 2 NO, 24..240 V AC/DC

Home ProductsIndustrialHarmonyModular temperature Control Relay

Harmony Control Relays, Modular temperature Control Relay, 5 A , 2 NO, 24..240 V AC/DC

Item Number: RM35ATR5MW

Datasheet

Barcode

Qty UoM EAN Colour
-
-
-

Specifications

Design

Range of product

Harmony Control Relays

Product or component type

elevator machine room temperature control relay

Sustainable offer status

Green Premium product

Warranty

18 months

Physical

Connections - terminals

screw connectors

[in] rated current

5 A

Width

35 mm

Marking

CE : EMC 89/336/EEC|CE : 73/23/EEC

Insulation resistance

> 500 MOhm at 500 V DC between supply and relay output conforming to IEC 60255-5|> 500 MOhm at 500 V DC between measurement and relay output conforming to IEC 60664-1|> 1 MOhm at 500 V DC between supply and measurement conforming to IEC 60255-5|> 500 MOhm at 500 V DC between supply and relay output conforming to IEC 60664-1|> 500 MOhm at 500 V DC between measurement and relay output conforming to IEC 60255-5|> 1 MOhm at 500 V DC between supply and measurement conforming to IEC 60664-1

Connections - terminals

screw terminals, 1 x 0.5...1 x 4 mm² (AWG 20...AWG 11) solid without cable end|screw terminals, 2 x 0.5...2 x 2.5 mm² (AWG 20...AWG 14) solid without cable end|screw terminals, 1 x 0.2...1 x 2.5 mm² (AWG 24...AWG 12) flexible with cable end|screw terminals, 2 x 0.2...2 x 1.5 mm² (AWG 24...AWG 16) flexible with cable end

Mounting support

35 mm symmetrical DIN rail conforming to IEC 60715

Electrical durability

100000 cycles

Mechanical durability

30000000 cycles

Control type

without test button

Standards

IEC 60255-6|NF EN 60255-6

Product certifications

GL|GOST|C-Tick|CSA|UL

Ambient air temperature for storage

-40...70 °C

Ambient air temperature for operation

-20...50 °C

Ip degree of protection

IP20 (terminals) conforming to IEC 60529|IP30 (casing) conforming to IEC 60529

Eu rohs directive

Pro-active compliance (Product out of EU RoHS legal scope)

Mercury free

Yes

Rohs exemption information

Yes

China rohs regulation

X

Environmental disclosure

ENVPEP1504008EN

Circularity profile

ENVEOLI1504008EN

California proposition 65

WARNING: This product can expose you to chemicals including: Lead and lead compounds, which is known to the State of California to cause cancer and birth defects or other reproductive harm. For more information go to www.P65Warnings.ca.gov

Material

Contacts material

cadmium free

Others

Commercial status history

SESA301466 | Wed Oct 25 00:50:00 EDT 2023 | From Import Local | From 18 to 19

Package 1 bare product quantity

1

Relay type

temperature control relays

Product specific application

for elevator machine rooms and 3-phase supplies

Relay name

RM35AT

Relay monitored parameters

overtemperature: 34...46°C|undertemperature: -1...11°C

Time delay range

0.1...10 s adjustable delay (tolerance: 0...10 % of the full scale value)

Switching capacity in va

1250 VA

Minimum switching current

10 mA at 5 V DC

Maximum power consumption in va

3.5 VA AC

Utilisation category

AC-12 conforming to IEC 60947-5-1|AC-13 conforming to IEC 60947-5-1|AC-14 conforming to IEC 60947-5-1|AC-15 conforming to IEC 60947-5-1|DC-12 conforming to IEC 60947-5-1|DC-13 conforming to IEC 60947-5-1|DC-14 conforming to IEC 60947-5-1

Time delay type

adjustable 1...10 s Tt- time delay upon fault

Measurement range

+/- 1...46 °C

[uc] control circuit voltage

24...240 V

Contacts type and composition

2 NO

Reset time

8 s

Maximum switching voltage

250 V AC/DC

[us] rated supply voltage

24...240 V AC/DC

[us] rated supply voltage

24...240 V AC/DC 50/60 Hz, non self-powered

Supply voltage limits

20.4...264 V AC|21.6...264 V DC

Maximum power consumption in w

0.6 W DC

Resistance across terminals

1.33 kOhm at temperature

Output contacts

2 NO

Nominal output current

5 A

Run-up delay at power-up

0.2 s

Measurement accuracy

+/- 2 °C

Response time

<= 3.5 s + Tt (in case of temperature fault)|<= 3.5 s (on disappearance of fault)

Temperature probe type

Pt 100 - 3-wire

Installed device

Pt 100 probe cable length <= 10 m

Overvoltage category

III conforming to IEC 60664-1

[ui] rated insulation voltage

250 V conforming to IEC 60664-1

Control circuit voltage limits

- 10 % + 10 % Un DC|- 15 % + 10 % Un AC

Supply frequency

50/60 Hz +/- 10 %

Insulation

galvanic insulation between supply and measurement

Operating position

any position without derating

Tightening torque

0.6...1 N.m conforming to IEC 60947...1

Housing material

self-extinguishing plastic

Status led

1 LED green for power ON|1 LED yellow for correct temperature (high R1)|1 LED yellow for correct temperature (low R2)

Operating rate

<= 360 operations/hour full load

Compatibility code

RM3

Immunity to microbreaks

10 ms

Electromagnetic compatibility

emission standard for industrial environments conforming to IEC 61000-6-4|emission standard for residential, commercial and light-industrial environments conforming to IEC 61000-6-3|immunity for industrial environments conforming to NF EN/IEC 61000-6-2

Vibration resistance

0.35 mm (f= 5-57.6 Hz) conforming to IEC 60068-2-6/IEC 60255-21-1|1 gn (f= 57.6-150 Hz) conforming to IEC 60068-2-6/IEC 60255-21-1

Shock resistance

15 gn for 11 ms conforming to IEC 60255-21-1

Pollution degree

3 conforming to IEC 60664-1

Dielectric test voltage

2 kV, 1 min AC 50 Hz

Non-dissipating shock wave

4 kV

Unit type of package 1

PCE

Number of units in package 1

1

Package 1 height

7.52 cm

Package 1 width

4.4 cm

Package 1 length

9.7 cm

Package 1 weight

131.0 g

Unit type of package 2

S03

Number of units in package 2

48

Package 2 height

30.0 cm

Package 2 width

30.0 cm

Package 2 length

40.0 cm

Package 2 weight

7.001 kg

Weee

The product must be disposed on European Union markets following specific waste collection and never end up in rubbish bins
Show all specifications

Documents & downloads

hide show
Filter items
  • All

  • CAD Files and Packs

  • Technical Data Catalogues

  • Installation Instruction

  • End of Life Manual

  • Environmental Disclosure

  • Technical illustration

  • Application Notes

  • eTechPub

  • Certificates (MSDS)

  • Declaration of Conformity