Harmony Control Relays, Modular multifunction 3-phase supply Control Relay, 5 A, 1 CO, 208...480 V AC

Home ProductsIndustrialHarmonyModular multifunction 3-phase supply Control Relay

Harmony Control Relays, Modular multifunction 3-phase supply Control Relay, 5 A, 1 CO, 208...480 V AC

Item Number: RM17TU00

Datasheet

Barcode

Qty UoM EAN Colour
-
-
-

Specifications

Design

Product or component type

3-phase control relay

Range of product

Harmony Control Relays

Warranty

18 months

Physical

Connections - terminals

screw connectors

[in] rated current

5 A

Insulation resistance

> 500 MOhm at 500 V DC conforming to IEC 60255-5|> 500 MOhm at 500 V DC conforming to IEC 60664-1

Connections - terminals

screw terminals, 1 x 0.5...1 x 4 mm² (AWG 20...AWG 11) solid without cable end|screw terminals, 2 x 0.5...2 x 2.5 mm² (AWG 20...AWG 14) solid without cable end|screw terminals, 1 x 0.2...1 x 2.5 mm² (AWG 24...AWG 12) flexible with cable end|screw terminals, 2 x 0.2...2 x 1.5 mm² (AWG 24...AWG 16) flexible with cable end

Local signalling

LED (green) for power ON|LED (yellow) for relay ON

Mounting support

35 mm symmetrical DIN rail conforming to IEC 60715

Electrical durability

100000 cycles

Mechanical durability

30000000 cycles

Width

17.5 mm

Net weight

0.13 kg

Control type

without test button

Standards

IEC 60255-1

Product certifications

GL|GOST|UL|C-Tick|CSA

Marking

CE

Ambient air temperature for storage

-40...70 °C

Ambient air temperature for operation

-20...50 °C

Relative humidity

95 % at 55 °C conforming to IEC 60068...2-30

Ip degree of protection

IP20 (terminals) conforming to IEC 60529|IP30 (casing) conforming to IEC 60529

Reach regulation

Reference contains Substances of Very High Concern above the threshold

Eu rohs directive

Pro-active compliance (Product out of EU RoHS legal scope)

Mercury free

Yes

Rohs exemption information

Yes

China rohs regulation

X

Environmental disclosure

ENVPEP1504008EN

Circularity profile

ENVEOLI1504008EN

California proposition 65

WARNING: This product can expose you to chemicals including: Lead and lead compounds, which is known to the State of California to cause cancer and birth defects or other reproductive harm. For more information go to www.P65Warnings.ca.gov

Others

Package 1 bare product quantity

1

Relay type

multifunction control relay

Product specific application

for 3-phase supply

Relay name

RM17TU

Relay monitored parameters

undervoltage detection|phase sequence|phase failure detection

Measurement range

208...480 V AC

Time delay type

adjustable 0.1...10 s, +/- 10 % of the full scale value Tt- time delay upon fault

Output contacts

1 C/O

Nominal output current

5 A

Contacts type and composition

1 C/O

[uc] control circuit voltage

208...480 V

[us] rated supply voltage

, self-powered

Supply voltage limits

183...528 V AC

Reset time

1500 ms time delay

Maximum switching voltage

250 V AC|250 V DC

Switching capacity in va

1250 VA

Minimum switching current

10 mA at 5 V DC

Maximum switching current

5 A AC|5 A DC

Control circuit voltage limits

- 12 % + 10 % Un

Power consumption in va

0...22 VA at 400 V AC 50 Hz

Control circuit frequency

50...60 Hz +/- 10 %

Measurement voltage limits

183...528 V AC

Hysteresis

2 %

Run-up delay at power-up

650 ms

Maximum measuring cycle

150 ms measurement cycle as true rms value

Threshold adjustment voltage

2...20 % of Un selected|-2...-12 % in the range 208 V AC|-2...-17 % in the range 220 V AC

Voltage range

208...480 V phase to phase

Repeat accuracy

0.5 % for input and measurement circuit|3 % for time delay

Measurement error

< 0.05 %/°C with temperature variation|< 1 % over the whole range with voltage variation

Phase failure sensitivity

0.7 Un

Response time

< 200 ms (in the event of a fault)

[ui] rated insulation voltage

400 V conforming to IEC 60664-1

Supply frequency

50/60 Hz +/- 10 %

Operating position

any position without derating

Tightening torque

0.6...1 N.m conforming to IEC 60947...1

Housing material

self-extinguishing plastic

Operating rate

<= 360 operations/hour full load

Utilisation category

AC-12 conforming to IEC 60947-5-1|AC-13 conforming to IEC 60947-5-1|AC-14 conforming to IEC 60947-5-1|AC-15 conforming to IEC 60947-5-1|DC-12 conforming to IEC 60947-5-1|DC-13 conforming to IEC 60947-5-1

Safety reliability data

MTTFd = 502.2 years|B10d = 470000

Functionality

undervoltage detection

Compatibility code

RM17

Electromagnetic compatibility

emission standard for industrial environments conforming to IEC 61000-6-4|emission standard for residential, commercial and light-industrial environments conforming to IEC 61000-6-3|immunity for industrial environments conforming to IEC 61000-6-2

Directives

73/23/EEC - low voltage directive|89/336/EEC - electromagnetic compatibility

Vibration resistance

0.35 mm (f= 5-57.6 Hz) conforming to IEC 60068-2-6|1 gn (f= 57.6-150 Hz) conforming to IEC 60255-21-1

Shock resistance

15 gn for 11 ms conforming to IEC 60255-21-1

Pollution degree

3 conforming to IEC 60664-1

Overvoltage category

III conforming to IEC 60664-1

Dielectric test voltage

2 kV, 1 min AC 50 Hz conforming to IEC 60255-5|2 kV, 1 min AC 50 Hz conforming to IEC 60664-1

Non-dissipating shock wave

4 kV conforming to IEC 60255-5|4 kV conforming to IEC 60664-1|4 kV conforming to IEC 61000-4-5

Unit type of package 1

PCE

Number of units in package 1

1

Package 1 height

2.8 cm

Package 1 width

8 cm

Package 1 length

9.6 cm

Package 1 weight

94 g

Unit type of package 2

S02

Number of units in package 2

48

Package 2 height

15 cm

Package 2 width

30 cm

Package 2 length

40 cm

Package 2 weight

5.003 kg

Scip number

ba9cbb5b-722a-41d2-b7d0-f60d5f3f104d

Take-back

No

Product contributes to saved and avoided emissions

No

Removable battery

N/A

Carbon footprint (kg.eq.co2 per cr, total life cycle)

99.0316984562
Show all specifications

Documents & downloads

hide show
Filter items
  • All

  • CAD Files and Packs

  • Technical Data Catalogues

  • Installation Instruction

  • Environmental Disclosure

  • End of Life Manual

  • Technical illustration

  • Application Notes

  • eTechPub

  • Certificates (MSDS)

  • Declaration of Conformity

Frequently Asked Questions

hide show

What is the overvoltage percentage for the zelio phase measurement relays part numbers RM17TU00 and RM17TE00

Issue: 
RM17TU00 and RM17TE00 Instruction sheet

Product Line:
Relays and Timers

Environment:
Zelio phase measurement relays

Resolution:
The overvoltage percentage is selectable from 2-20% of the supply voltage Un.