Harmony Control Relays, Modular liquid level Control Relay, 5A, 2CO, 24...240V AC DC

Home ProductsIndustrialHarmonyModular liquid level Control Relay

Harmony Control Relays, Modular liquid level Control Relay, 5A, 2CO, 24...240V AC DC

Item Number: RM35LM33MW

Datasheet

Barcode

Qty UoM EAN Colour
-
-
-

Specifications

Design

Range of product

Harmony Control Relays

Product or component type

level control relay

Warranty

18 months

Physical

Connections - terminals

screw connectors

[in] rated current

5 A

Marking

CE : 73/23/EEC|CE : EMC 89/336/EEC

Insulation resistance

> 500 MOhm at 500 V DC between supply and relay output conforming to IEC 60255-5|> 500 MOhm at 500 V DC between measurement and relay output conforming to IEC 60664-1|> 1 MOhm at 500 V DC between supply and measurement conforming to IEC 60255-5|> 500 MOhm at 500 V DC between supply and relay output conforming to IEC 60664-1|> 500 MOhm at 500 V DC between measurement and relay output conforming to IEC 60255-5|> 1 MOhm at 500 V DC between supply and measurement conforming to IEC 60664-1

Connections - terminals

screw terminals, 1 x 0.5...1 x 4 mm² (AWG 20...AWG 11) solid without cable end|screw terminals, 2 x 0.5...2 x 2.5 mm² (AWG 20...AWG 14) solid without cable end|screw terminals, 2 x 0.2...2 x 1.5 mm² (AWG 24...AWG 16) flexible with cable end|screw terminals, 1 x 0.2...1 x 2.5 mm² (AWG 24...AWG 12) flexible with cable end

Local signalling

LED (yellow) for relay ON|LED (green) for power ON|LED (yellow) for timer ON

Mounting support

35 mm symmetrical DIN rail conforming to IEC 60715

Electrical durability

100000 cycles

Mechanical durability

30000000 cycles

Width

35 mm

Control type

without test button

Standards

IEC 60255-6

Product certifications

CSA|GL|UL|C-Tick|GOST

Ambient air temperature for storage

-40...70 °C

Ambient air temperature for operation

-20...50 °C

Relative humidity

95 % at 55 °C conforming to IEC 60068...2-30

Ip degree of protection

IP20 (terminals) conforming to IEC 60529|IP30 (casing) conforming to IEC 60529

Reach regulation

Reference contains Substances of Very High Concern above the threshold

Eu rohs directive

Pro-active compliance (Product out of EU RoHS legal scope)

Mercury free

Yes

China rohs regulation

X

Environmental disclosure

ENVPEP1504008EN

Circularity profile

ENVEOLI1504008EN

California proposition 65

"WARNING: This product can expose you to chemicals including: Lead and lead compounds, which is known to the State of California to cause cancer and birth defects or other reproductive harm. For more information go to www.P65Warnings.ca.gov"

Others

Package 1 bare product quantity

1

Package 2 bare product quantity

48

Package 3 bare product quantity

384

Relay type

level control relay

Relay name

RM35L

Relay monitored parameters

detection by resistive probes

Time delay type

adjustable 0.1...5 s, +/- 10 % Tt- time delay upon fault

Switching capacity in va

1250 VA

Minimum switching current

10 mA at 5 V DC

Maximum switching current

5 A AC/DC

Maximum power consumption in va

5 VA AC

Measurement range

250 Ohm...1 MOhm

Utilisation category

AC-12 conforming to IEC 60947-5-1|AC-13 conforming to IEC 60947-5-1|AC-14 conforming to IEC 60947-5-1|AC-15 conforming to IEC 60947-5-1|DC-12 conforming to IEC 60947-5-1|DC-13 conforming to IEC 60947-5-1

Contacts type and composition

2 C/O

[uc] control circuit voltage

24...240 V

Reset time

1750 ms

Maximum switching voltage

250 V AC/DC

[us] rated supply voltage

24...240 V AC/DC 50/60 Hz, non self-powered

Supply voltage limits

20.4...264 V AC/DC

Control circuit voltage limits

- 15 % + 10 % Un

Maximum power consumption in w

1.5 W DC

Output contacts

2 C/O

Nominal output current

5 A

Run-up delay at power-up

0.6 s

Measurement accuracy

+/- 10 % of the full scale value|+/- 20 % for the HS range

Repeat accuracy

+/- 2 % for time delay

Measurement error

0.5 %/°C with temperature variation

Sensitivity scale

0.25...5 kOhm LS (Low Sensitivity)|5...100 kOhm St (Standard Sensitivity)|50...1000 kOhm HS (High Sensitivity)

Sensitivity adjustment

5...100 %

Maximum supply current for sensors

1 mA

Cable capacitance

1 nF at HS (High Sensitivity) for probe cable|2.2 nF at St (Standard Sensitivity) for probe cable|4.7 nF at LS (Low Sensitivity)

Overvoltage category

III conforming to IEC 60664-1

[ui] rated insulation voltage

250 V conforming to IEC 60664-1

[uimp] rated impulse withstand voltage

4 kV conforming to IEC 60255-5|4 kV conforming to IEC 60664-1|4 kV conforming to IEC 61000-4-5

Operating position

any position without derating

Tightening torque

0.6...1 N.m conforming to IEC 60947...1

Housing material

self-extinguishing plastic

Operating rate

<= 360 operations/hour full load

Measurement range

0.25...1000 kOhm

Safety reliability data

B10d = 170000|MTTFd = 182.6 years

Functionality

resistive probe detection

Compatibility code

RM3

Immunity to microbreaks

100 ms DC|90 ms AC

Electromagnetic compatibility

emission standard for industrial environments conforming to IEC 61000-6-4|emission standard for residential, commercial and light-industrial environments conforming to IEC 61000-6-3|immunity for industrial environments conforming to NF EN/IEC 61000-6-2

Pollution degree

3 conforming to IEC 60664-1

Dielectric test voltage

2 kV, 1 min AC 50 Hz conforming to IEC 60255-5|2 kV, 1 min AC 50 Hz conforming to IEC 60664-1

Unit type of package 1

PCE

Number of units in package 1

1

Package 1 height

4.400 cm

Package 1 width

7.800 cm

Package 1 length

9.500 cm

Package 1 weight

134.000 g

Unit type of package 2

S03

Number of units in package 2

48

Package 2 height

30.000 cm

Package 2 width

30.000 cm

Package 2 length

40.000 cm

Package 2 weight

7.155 kg

Unit type of package 3

P06

Number of units in package 3

384

Package 3 height

75.000 cm

Package 3 width

60.000 cm

Package 3 length

80.000 cm

Package 3 weight

65.660 kg
Show all specifications

Documents & downloads

hide show
Filter items
  • All

  • CAD Files and Packs

  • Technical Data Catalogues

  • Installation Instruction

  • End of Life Manual

  • Environmental Disclosure

  • Technical illustration

  • Technical Drawing

  • Application Notes

  • Certificates (MSDS)

  • eTechPub

  • Declaration of Conformity