Harmony Control Relays, Modular 1 phase current Control Relay, 5A, 2CO, 2…500mA, 24…240V AC DC

Home ProductsIndustrialHarmonyModular 1 phase current Control Relay

Harmony Control Relays, Modular 1 phase current Control Relay, 5A, 2CO, 2…500mA, 24…240V AC DC

Item Number: RM35JA31MW

Datasheet

Barcode

Qty UoM EAN Colour
-
-
-

Specifications

Design

Range of product

Harmony Control Relays

Product or component type

current control relay

Warranty

18 months

Physical

Connections - terminals

screw connectors

[in] rated current

5 A

Marking

CE : EMC 89/336/EEC|CE : 73/23/EEC

Insulation resistance

> 500 MOhm at 500 V DC between supply and relay output conforming to IEC 60255-5|> 500 MOhm at 500 V DC between measurement and relay output conforming to IEC 60664-1|> 1 MOhm at 500 V DC between supply and measurement conforming to IEC 60255-5|> 500 MOhm at 500 V DC between supply and relay output conforming to IEC 60664-1|> 500 MOhm at 500 V DC between measurement and relay output conforming to IEC 60255-5|> 1 MOhm at 500 V DC between supply and measurement conforming to IEC 60664-1

Connections - terminals

screw terminals, 1 x 0.5...1 x 4 mm² (AWG 20...AWG 11) solid without cable end|screw terminals, 2 x 0.5...2 x 2.5 mm² (AWG 20...AWG 14) solid without cable end|screw terminals, 1 x 0.2...1 x 2.5 mm² (AWG 24...AWG 12) flexible with cable end|screw terminals, 2 x 0.2...2 x 1.5 mm² (AWG 24...AWG 16) flexible with cable end

Local signalling

LED (green) for power ON|LED (yellow) for relay ON

Mounting support

35 mm symmetrical DIN rail conforming to IEC 60715

Electrical durability

100000 cycles

Mechanical durability

30000000 cycles

Width

35 mm

Control type

without test button

Net weight

0.13 kg

Standards

IEC 60255-6

Product certifications

GL|CSA|GOST|UL|C-Tick

Ambient air temperature for storage

-40...70 °C

Ambient air temperature for operation

-20...50 °C

Relative humidity

95 % at 55 °C conforming to IEC 60068...2-30

Ip degree of protection

IP20 (terminals) conforming to IEC 60529|IP30 (casing) conforming to IEC 60529

Reach regulation

Reference contains Substances of Very High Concern above the threshold

Eu rohs directive

Pro-active compliance (Product out of EU RoHS legal scope)

Mercury free

Yes

China rohs regulation

X

Environmental disclosure

ENVPEP1504008EN

Circularity profile

ENVEOLI1504008EN

California proposition 65

"WARNING: This product can expose you to chemicals including: Lead and lead compounds, which is known to the State of California to cause cancer and birth defects or other reproductive harm. For more information go to www.P65Warnings.ca.gov"

Material

Contacts material

cadmium free

Others

Package 1 bare product quantity

1

Package 2 bare product quantity

48

Relay type

current control relay

Relay name

RM35JA

Time delay type

adjustable 0.3...30 s, 0 + 10 % Tt- time delay upon fault|adjustable 1...20 s, 0 + 10 % Ti- inhibition time delay upon startup

Switching capacity in va

1250 VA

Minimum switching current

10 mA at 5 V DC

Maximum switching current

5 A AC

Maximum power consumption in va

3.5 VA AC

Measurement range

2...500 mA AC/DC E2-M terminals

Utilisation category

AC-12 conforming to IEC 60947-5-1|AC-13 conforming to IEC 60947-5-1|AC-14 conforming to IEC 60947-5-1|AC-15 conforming to IEC 60947-5-1|DC-12 conforming to IEC 60947-5-1|DC-13 conforming to IEC 60947-5-1|DC-14 conforming to IEC 60947-5-1

Contacts type and composition

2 C/O

[uc] control circuit voltage

24...240 V

Reset time

1500 ms time delay

Maximum switching voltage

250 V AC

Supply voltage limits

20.4...264 V AC/DC

Control circuit voltage limits

- 15 % + 10 % Un

Maximum power consumption in w

0.6 W DC

Control circuit frequency

40...70 Hz +/- 10 %

Resistance across terminals

1 Ohm at E2-M terminals|5 Ohm at E1-M terminals|0.2 Ohm at E3-M terminals

Output contacts

2 C/O

Nominal output current

5 A

Maximum measuring cycle

30 ms measurement cycle as true rms value

Hysteresis

5...50 % of threshold setting

Run-up delay at power-up

0.3 s

Measurement accuracy

+/- 10 % of the full scale value

Repeat accuracy

+/- 0.5 % for input and measurement circuit|+/- 2 % for time delay

Measurement error

0.05 %/°C with temperature variation|1 by volt over the whole range with voltage variation

Polarity

no DC

Threshold setting

10...100 %

Overvoltage category

III conforming to IEC 60664-1

[ui] rated insulation voltage

250 V conforming to IEC 60664-1

Operating position

any position without derating

Tightening torque

0.6...1 N.m conforming to IEC 60947...1

Housing material

self-extinguishing plastic

Operating rate

<= 360 operations/hour full load

[us] rated supply voltage

24...240 V AC/DC 50/60 Hz, non self-powered

Safety reliability data

MTTFd = 296.8 years|B10d = 270000

Functionality

overcurrent or undercurrent in window mode

Compatibility code

RM3

Immunity to microbreaks

50 ms

Electromagnetic compatibility

emission standard for industrial environments conforming to IEC 61000-6-4|emission standard for residential, commercial and light-industrial environments conforming to IEC 61000-6-3|immunity for industrial environments conforming to NF EN/IEC 61000-6-2

Vibration resistance

0.35 mm (f= 5-57.6 Hz) conforming to IEC 60068-2-6|1 gn (f= 57.6-150 Hz) conforming to IEC 60255-21-1

Shock resistance

15 gn for 11 ms conforming to IEC 60255-21-1

Pollution degree

3 conforming to IEC 60664-1

Dielectric test voltage

2 kV, 1 min AC 50 Hz conforming to IEC 60255-5|2 kV, 1 min AC 50 Hz conforming to IEC 60664-1

Non-dissipating shock wave

4 kV conforming to IEC 60255-5|4 kV conforming to IEC 60664-1|4 kV conforming to IEC 61000-4-5

Unit type of package 1

PCE

Number of units in package 1

1

Package 1 height

4.500 cm

Package 1 width

7.800 cm

Package 1 length

9.500 cm

Package 1 weight

138.000 g

Unit type of package 2

S03

Number of units in package 2

48

Package 2 height

30.000 cm

Package 2 width

30.000 cm

Package 2 length

40.000 cm

Package 2 weight

7.350 kg

Weee

The product must be disposed on European Union markets following specific waste collection and never end up in rubbish bins
Show all specifications

Documents & downloads

hide show
Filter items
  • All

  • CAD Files and Packs

  • Technical Data Catalogues

  • Installation Instruction

  • End of Life Manual

  • Environmental Disclosure

  • Technical illustration

  • Application Notes

  • Certificates (MSDS)

  • eTechPub

  • Declaration of Conformity

Frequently Asked Questions

hide show

Can we provide an instruction sheet for a RM35JA32MW?

Issue:
How do you adjust the RM35JA32MW?

Product Line:  
Current measurement relay

Environment: 
RM35JA31MW, RM35JA32MW

Cause: 
Need instructions to set up relay.

Resolution:  
See attached instruction sheet.