Issue:
PT100 probe to measure temperature
Product Line:
ATV61 and ATV71
Environment:
All models and serial numbers
Cause:
None
Resolution:
No, LI6 is a digital input and cannot read a resistance or an analog value. LI6 can be used in conjunction with a PTC. The input is activated when the resistance of the PTC reaches 3k ohms.
It is not designed to accept a PT100 probe.
ATV630 can do this.
PT100 probe to measure temperature
Product Line:
ATV61 and ATV71
Environment:
All models and serial numbers
Cause:
None
Resolution:
No, LI6 is a digital input and cannot read a resistance or an analog value. LI6 can be used in conjunction with a PTC. The input is activated when the resistance of the PTC reaches 3k ohms.
It is not designed to accept a PT100 probe.
ATV630 can do this.
Refer the attachment for the internal wiring connection of Motor Mechanism Module (MT100 to MT630) for Compact NS < 630 Moulded Case Circuit Breaker (MCCB).
Issue:
Time current curves for H and J MCP
Product Line:
Circuit Breakers
Resolution:
Attached are the trip curves for the Powerpact H and J motor circuit protectors (from document 0611CT1001).
Time current curves for H and J MCP
Product Line:
Circuit Breakers
Resolution:
Attached are the trip curves for the Powerpact H and J motor circuit protectors (from document 0611CT1001).
- When using Manual Settings, use trip curve 045-1.