Altistart 01, Soft starter for asynchronous motor, ATS01, 9 A-110..480V-1.1..4 KW

Home ProductsIndustrialAltistartSoft starter for asynchronous motor

Altistart 01, Soft starter for asynchronous motor, ATS01, 9 A-110..480V-1.1..4 KW

Item Number: ATS01N109FT

Datasheet

Product Dimensions

Width icon

Width45 mm

Height icon

Height124 mm

Depth icon

Depth131 mm

Barcode

Qty UoM EAN Colour
-
-
-

Specifications

Design

Range of product

Altistart 01

Product or component type

soft starter

Product destination

asynchronous motors

Warranty

18 months

Physical

Function available

integrated bypass

Marking

CE

Height

124 mm

Width

45 mm

Depth

131 mm

Net weight

0.28 kg

Standards

EN/IEC 60947-4-2

Product certifications

C-Tick|GOST|CSA|CCC|UL

Ip degree of protection

IP20

Relative humidity

5...95 % without condensation or dripping water conforming to EN/IEC 60068...2-3

Ambient air temperature for operation

-10...40 °C (without derating)|40...50 °C (with current derating of 2 % per °C)

Ambient air temperature for storage

-25...70 °C conforming to EN/IEC 60947...4-2

Reach regulation

Free of Substances of Very High Concern above the threshold

Reach free of svhc

Yes

Eu rohs directive

Pro-active compliance (Product out of EU RoHS legal scope)

Toxic heavy metal free

Yes

Mercury free

Yes

Rohs exemption information

Yes

China rohs regulation

X

California proposition 65

"WARNING: This product can expose you to chemicals including: Lead and lead compounds, which is known to the State of California to cause cancer and birth defects or other reproductive harm. For more information go to www.P65Warnings.ca.gov"

Others

Life cycle assessment data

No

If one of the deliverables is not relevant please give the reason

Brand Labelling

Substance regulation data deliverable

Yes

Package 1 bare product quantity

1

Package 2 bare product quantity

14

Package 3 bare product quantity

112

Product specific application

simple machine

Device short name

ATS01

Network number of phases

1 phase

[us] rated supply voltage

110...480 V - 10...10 %

Motor power kw

4 kW, 3 phases at 400 V|1.5 kW, 3 phases at 230 V|1.1 kW, 1 phase at 230 V

Motor power hp

1 hp, 3 phases at 210 V|2 hp, 3 phases at 230 V|5 hp, 3 phases at 460 V

Icl starter rating

9 A

Utilisation category

AC-53B conforming to EN/IEC 60947-4-2

Current consumption

45 A at nominal load

Type of start

start with voltage ramp

Power dissipation in w

1 W at full load and at end of starting|46 W in transient state

Assembly style

with heat sink

Supply voltage limits

99...528 V

Supply frequency

50...60 Hz - 5...5 %

Network frequency

47.5...63 Hz

Output voltage

<= power supply voltage

[uc] control circuit voltage

110 V AC +/- 10 % at 35 mA|24 V AC/DC +/- 10 % at 30 mA|240 V AC +/- 10 % at 80 mA

Starting time

1 s / 100 |5 s / 20 |adjustable from 1 to 5 s

Starting torque

30...80 % of starting torque of motor connected directly on the line supply

Discrete output current

2 A DC-13|3 A AC-15

Tightening torque

0.5...0.5 N.m|1.9...2.5 N.m

Electrical connection

4 mm screw clamp terminal - rigid 1 1...10 mm² AWG 8 power circuit|screw connector - rigid without cable end 1 0.5...2.5 mm² AWG 14 control circuit|4 mm screw clamp terminal - rigid 2 1...6 mm² AWG 10 power circuit|screw connector - rigid 2 0.5...1 mm² AWG 17 control circuit|screw connector - flexible with cable end 1 0.5...1.5 mm² AWG 16 control circuit|4 mm screw clamp terminal - flexible without cable end 1 1.5...10 mm² AWG 8 power circuit|screw connector - flexible without cable end 1 0.5...2.5 mm² AWG 14 control circuit|4 mm screw clamp terminal - flexible with cable end 2 1...6 mm² AWG 10 power circuit|4 mm screw clamp terminal - flexible without cable end 2 1.5...6 mm² AWG 10 power circuit|screw connector - flexible without cable end 2 0.5...1.5 mm² AWG 16 control circuit

Operating position

vertical +/- 10 degree

Compatibility code

ATS01N1

Power range

1.1...2 kW at 200...240 V 1 phase|2.2...3 kW at 200...240 V 3 phases|4...6 kW at 380...440 V 3 phases

Motor starter type

soft starter

Electromagnetic compatibility

conducted and radiated emissions level B conforming to CISPR 11|conducted and radiated emissions level B conforming to IEC 60947-4-2|damped oscillating waves level 3 conforming to IEC 61000-4-12|electrostatic discharge level 3 conforming to IEC 61000-4-2|EMC immunity level 3 conforming to EN 50082-1|EMC immunity level B conforming to EN 50082-2|harmonics level 3 conforming to IEC 1000-3-2|harmonics level 3 conforming to IEC 1000-3-4|immunity to conducted interference caused by radio-electrical fields level 3 conforming to IEC 61000-4-6|immunity to electrical transients level 4 conforming to IEC 61000-4-4|immunity to radiated radio-electrical interference level 3 conforming to IEC 61000-4-3|micro-cuts and voltage fluctuation conforming to IEC 61000-4-11|voltage/current impulse level 3 conforming to IEC 61000-4-5

Pollution degree

2 conforming to EN/IEC 60947-4-2

Vibration resistance

1 gn (f= 13-150 Hz) conforming to EN/IEC 60068-2-6|1.5 mm peak to peak (f= 3-13 Hz) conforming to EN/IEC 60068-2-6

Shock resistance

15 gn for 11 ms conforming to EN/IEC 60068-2-27

Operating altitude

<= 1000 m without derating|> 1000 m with current derating of 2.2 % per additional 100 m

Unit type of package 1

PCE

Number of units in package 1

1

Package 1 height

5.300 cm

Package 1 width

15.000 cm

Package 1 length

17.000 cm

Package 1 weight

341.000 g

Unit type of package 2

S03

Number of units in package 2

14

Package 2 height

30.000 cm

Package 2 width

30.000 cm

Package 2 length

40.000 cm

Package 2 weight

5.377 kg

Unit type of package 3

P06

Number of units in package 3

112

Package 3 height

75.000 cm

Package 3 width

60.000 cm

Package 3 length

80.000 cm

Package 3 weight

56.620 kg

Weee

The product must be disposed on European Union markets following specific waste collection and never end up in rubbish bins
Show all specifications

Documents & downloads

hide show
Filter items
  • All

  • CAD Files and Packs

  • Technical Data Catalogues

  • Installation Instruction

  • End of Life Manual

  • Technical Drawing

  • Certificates (MSDS)

  • Declaration of Conformity

  • eTechPub

Frequently Asked Questions

hide show

What are the adjustment ranges for the dials on an ATS01N1..FT?

What are the adjustment ranges for the dials on an ATS01N1..FT?  

Issue : 
Adjustment ranges for Schneider-Electric recommend for Altistart Soft Starters?

Product Line : 
Altistart Soft Starters

Environment : 
Open style Soft Starters

Cause : 
Adjustment Range

Resolution : 
For the START TIME dial, setpoint A is 1second and setpoint E is 5seconds.  There is a linear relationship from A to E setpoints.
For the INITIAL VOLTAGE dial, setpoint A is 30% and setpoint E is 80% of full voltage.  There is a linear relationship from A to E setpoints.