Altistart 01 Soft starter for asynchronous motor ATS01, 6 A-110..480V-0.75..3 KW

Home ProductsIndustrialAltistartSoft starter for asynchronous motor

Altistart 01 Soft starter for asynchronous motor

Item Number: ATS01N106FT

Retail
N/A
RRP (Inc. GST)

Datasheet

PDF datasheet

For ATS01N106FT

Product Dimensions

Width icon

Width23 mm

Height icon

Height100 mm

Depth icon

Depth100 mm

Barcode

Qty UoM EAN Colour
1 3389110667141 -

Specifications

Design

Range of product

Altistart 01

Product or component type

soft starter

Product destination

asynchronous motors

Warranty

18 months

Physical

[ue] rated operational voltage

  • 400 V 3 kW
  • 230 V 0.75 kW
  • 230 V 1.1 kW
  • 400 V 2.2 kW
  • 230 V 1 hp
  • 460 V 2 hp
  • 460 V 3 hp
  • 230 V 1.5 hp

Function available

integrated bypass

Marking

CE

Height

100 mm

Width

23 mm

Depth

100 mm

Net weight

0.16 kg

Standards

EN/IEC 60947-4-2

Product certifications

  • C-Tick
  • CCC
  • CSA
  • UL
  • GOST

Ip degree of protection

IP20

Relative humidity

5...95 % without condensation or dripping water conforming to EN/IEC 60068...2-3

Ambient air temperature for operation

  • -10...40 °C (without derating)
  • 40...50 °C (with current derating of 2 % per °C)

Ambient air temperature for storage

-25...70 °C conforming to EN/IEC 60947...4-2

China rohs regulation

X

California proposition 65

WARNING: This product can expose you to chemicals including: Lead and lead compounds, which is known to the State of California to cause cancer and birth defects or other reproductive harm. For more information go to www.P65Warnings.ca.gov
Show all specifications

Documents & downloads

hide show
Filter items
  • All

  • CAD Files and Packs

  • Technical Data Catalogues

  • Installation Instruction

  • End of Life Manual

  • Technical Drawing

  • eTechPub

  • Certificates (MSDS)

  • Declaration of Conformity

  • Page 2  /  3
  • Page 3  /  3

Frequently Asked Questions

hide show

Does the ATS01 come with a shorting contactor?

Issue:
Does the ATS01 have an internal shorting contactor?

Product Line:
Altistat 01

Environment:
All

Cause:
N/A

Resolution:
All of the ALTISTART 01 models, except the ATS01N103FT and ATS01N106FT, have an internal shorting contactor as standard.

What is the combination SCCR rating for ATSU01 with the U-Line starters?

Issue:
Customer is using the ATSU01 with the mounted Tesys U-Line motor starter. They are looking to coordinate the short circuit current rating.

Product line:
ATSU01, U-Line, Altistart 01, ATS01

Environment:
All models.

Cause:
n/a

Resolution:
Per Product Marketing, we do not have any combination SCCR ratings for the ATSU01 and U-Line devices. The ATSU01 and ATS01 have a standalone rating of 5kA. Except the ATS01N103FT and ATS01N106FT, which are 1kA. 
 

What are the adjustment ranges for the dials on an ATS01N1..FT?

What are the adjustment ranges for the dials on an ATS01N1..FT?  

Issue : 
Adjustment ranges for Schneider-Electric recommend for Altistart Soft Starters?

Product Line : 
Altistart Soft Starters

Environment : 
Open style Soft Starters

Cause : 
Adjustment Range

Resolution : 
For the START TIME dial, setpoint A is 1second and setpoint E is 5seconds.  There is a linear relationship from A to E setpoints.
For the INITIAL VOLTAGE dial, setpoint A is 30% and setpoint E is 80% of full voltage.  There is a linear relationship from A to E setpoints.