BCPM (Branch Circuit Power Meter), 1000A Split core CT, 0.333V Output, SZ 4

BCPM (Branch Circuit Power Meter), 1000A Split core CT, 0.333V Output, SZ 4

Item Number: LVCT01004S

This low-voltage split-core current transformer is part of PowerLogic BCPM (Branch Circuit Power Meter). It is Ideal for retrofit applications with Schneider Electric energy meters which accept low voltage current transducer input It is rated for a 1000A circuit. 0.333 V output, size 4. Split core opening is 62 mm x 201 mm.

Datasheet

Product Dimensions

Width icon

Widthinternal: 62 mm|external: 151 mm

Height icon

Heightinternal: 139 mm|external: 201 mm

Depth icon

Depth30 mm

Barcode

Qty UoM EAN Colour
-
-
-

Specifications

Design

Range

PowerLogic

Range of product

PowerLogic

Product or component type

current transformer

Product destination

BCPM|BCPMSC|Enercept|iEM3000|EM3500|EM4200|EM4900

Warranty

18 months

Physical

[in] rated current

1000 A

Range compatibility

PowerLogic PowerLogic BCPM BCPMA multi-circuit energy meter|PowerLogic PowerLogic BCPM BCPMB multi-circuit energy meter|PowerLogic PowerLogic BCPM BCPME multi-circuit energy meter|PowerLogic PowerLogic BCPMSC BCPMSCA multi-circuit energy meter|PowerLogic PowerLogic BCPMSC BCPMSCB multi-circuit energy meter|PowerLogic PowerLogic BCPMSC BCPMSCE multi-circuit energy meter|PowerLogic PowerLogic EM3500 EM3502 energy meter|PowerLogic PowerLogic EM3500 EM3550 energy meter|PowerLogic PowerLogic EM3500 EM3555 energy meter|PowerLogic PowerLogic EM3500 EM3560 energy meter|PowerLogic PowerLogic EM3500 EM3561 energy meter|PowerLogic PowerLogic EM4200 EM4235 energy meter|PowerLogic PowerLogic EM4200 EM4236 energy meter|PowerLogic PowerLogic EM4900 EM4904 multi-circuit energy meter|PowerLogic PowerLogic EM4900 EM4908 multi-circuit energy meter|PowerLogic PowerLogic EM4900 EM4914 multi-circuit energy meter|PowerLogic PowerLogic EM4900 EM4928 multi-circuit energy meter|Acti 9 Acti9 iEM3000 iEM3455 energy meter|Acti 9 Acti9 iEM3000 iEM3465 energy meter

Relative humidity

95 %

Ambient air temperature for operation

-15...60 °C

Ambient air temperature for storage

-40...70 °C

Width

internal: 62 mm|external: 151 mm

Depth

30 mm

Height

internal: 139 mm|external: 201 mm

Net weight

0.87 kg

Reach regulation

Free of Substances of Very High Concern above the threshold

Reach free of svhc

Yes

Eu rohs directive

Compliant

Toxic heavy metal free

Yes

Mercury free

Yes

Rohs exemption information

Yes

China rohs regulation

X

California proposition 65

"WARNING: This product can expose you to chemicals including: Lead and lead compounds, which is known to the State of California to cause cancer and birth defects or other reproductive harm. For more information go to www.P65Warnings.ca.gov"

Others

Package 1 bare product quantity

1

Device short name

LVCT

Output voltage

0.333 V

Electrical connection

cable: 1.8 m (AWG 18) 600 V

Accessory / separate part category

measurement accessory

Current transformer type

split core balance

Network frequency

50/60 Hz

Measurement accuracy

1 % 10...100 %

Compatibility code

LVCT

Unit type of package 1

PCE

Number of units in package 1

1

Package 1 height

10.2 cm

Package 1 width

21.0 cm

Package 1 length

25.4 cm

Package 1 weight

1.224 kg
Show all specifications