Clipsal - General Accessories, Nuts, No.6 Nc Square Nut

Clipsal - General Accessories, Nuts, No.6 Nc Square Nut

Item Number: 359

Datasheet

Barcode

Qty UoM EAN Colour
-
-
-

Specifications

Design

Product brand

Clipsal

Sustainable offer status

Green Premium product

Physical

Reach regulation

Reference contains Substances of Very High Concern above the threshold

Eu rohs directive

Compliant with Exemptions

Mercury free

Yes

Rohs exemption information

Yes

China rohs regulation

Product out of China RoHS scope. Substance declaration for your information

Environmental disclosure

ENVPEP060307EN

Circularity profile

N/A

Others

Package 1 bare product quantity

1

Unit type of package 1

PCE

Number of units in package 1

1

Package 1 height

3 cm

Package 1 width

10 cm

Package 1 length

8 cm

Package 1 weight

102 g
Show all specifications

Frequently Asked Questions

hide show

What is the difference between S33595 full function test kit and S33594 hand-held test kit

Product Line:
Circuit Breaker Test Set

Resolution:
HHTK - The S33594 hand-held test kit will test the trip function of the breaker and may be used for inhibiting ground fault and thermal imaging, and enable zone selective interlocking (ZSI) self restraint during primary injection testing.

FFTK - The S33595 full function test kit will test LSIG functions as well as the same functions as listed above.

Additional details below:
Test kit descriptions

Can the Micrologic X internal battery (LV833593SP) be replaced while breaker is energised?

Please see the below information from the LV833593SP Instruction Sheet.

image.png

The internal battery is dedicated to the supply of the trip causes LEDs and the internal clock, and there is no effect to the protection setting of the breaker.
Please see below description from the Masterpact MTZ Catalogue.
image.png

Are EasyPact MVS circuit breakers for sale in the USA or Canada?

Issue:
Where can I buy a EasyPact MVS breaker?

Product Line:
EasyPact MVS circuit breakers

Resolution:
There are no plans for a general release of the EasyPact MVS circuit breaker line in the US.
 

Masterpact breaker passes all FFTK tests except for ground fault, yet produces error codes on the trip unit; what is the problem?

PRODUCT LINE
Masterpact NW

RESOLUTION
Find out if this breaker is used in a MDGF (Modified Differential Ground Fault) system. If so, disconnect wire going to M1 on the secondary block and retest. M1 enables MDGF and disables residual GF, and removing it puts the breaker back into residual mode where it can be tested with the FFTK.

Can the Micrologic FFTK (Full Function Test Kit) be repaired?

Product Line:
Micrologic test equipment

Environment:
Electrical Distribution Equipment

Resolution:
Yes, the FFTK can be repaired in most cases. Have the distributor contact Customer Service for a "Return for Repair" RMA and send it back.
(see internal FA289579)

How can calibration of the S33595 be checked?

Product Line:
Circuit Breaker

Resolution:
The calibration of the test set is checked each time it is used. The S33595 microprocessor is designed with a power-up self check sequence. Each time the unit is powered up, it does a self diagnostic. This checks the health of all electronics, as well as positions of relays and switches inside the test kit. The self diagnostic also checks communications to the screen and the voltage level supplying the test kit. The test kit will not proceed to the test screens until all of these are verified.

The test kit also looks at calibration before each secondary injection test and if the microprocessor determines that it cannot reliably inject the correct signal, an error message will appear on the screen "Test kit calibration error, Test aborted".  When this occurs, the test kit must be returned to the factory for repair. Return through your local Schneider Electric (Square D) distributor.

For more details see instruction bulletin for the FFTK:
http://www.schneider-electric.us/en/download/document/48049-183-06/