Clipsal - 900 Series, Plug, Side Entry, 3 PIN, 10A

Clipsal - 900 Series, Plug, Side Entry, 3 PIN, 10A White

Item Number: 901-WH

Datasheet

Barcode

Qty UoM EAN Colour
-
-
-

Specifications

Design

Range of product

Series 900|PDL

Product brand

Clipsal

Colour

white

Physical

[in] rated current

10 A

[ue] rated operational voltage

230 V 50/60 Hz conforming to EN 60309-2

Others

Voltage colour

blue

Plug, socket, control station shape

angled

Duration

6 h

Unit type of package 1

PCE

Number of units in package 1

1
Show all specifications

Frequently Asked Questions

hide show

Will the LAD** time delay auxiliary contact module fit the D2 series pre-Tesys contactors?

Issue:
Can new accessories be used on older style contactors

Product Line:
IEC contactors and starters

Environment:
Pre-Tesys Contactors

Cause:
Identifying product compatibility

Resolution:
Yes, all front mount D2 and Tesys series auxiliary modules are backward forward compatible.

Video: What auxiliary contact modules are available for the LC1D and LC2D contactors?

Issue:
Auxiliary contact modules for the LC1D and LC2D contactors

Product Line: 
Contactor and Starters - IEC

Environment:
North American Products

Resolution:
Select based on application requirements. Please note that the TeSys and Pre-TeSys auxiliary blocks are backward/forward compatible.
Front Mounting; maximum of 1 block per contactor:

N.O.-------N.C.-----TeSys P/N--------Pre-TeSys P/N
--1-----------1---------LADN11-----------LA1DN11
--1-----------1---------LADN11G---------LA1DN11G (See Footnote 1)
--1-----------1---------LADN11P---------LA1DN11P (See Footnote 1)
--2-----------0---------LADN20-----------LA1DN20
--2-----------0---------LA1DX20---------LA1DX20 (See Footnote 2)
--2-----------0---------LA1DY20---------LA1DY20 (See Footnote 3)
--0-----------2---------LADN02-----------LA1DN02
--2-----------2---------LADN22-----------LA1DN22
--2-----------2---------LADN22G---------LA1DN22G (See Footnote 1)
--2-----------2---------LADN22P---------LA1DN22P (See Footnote 1)
--2-----------2---------LADC22------------LA1DC22 (See Footnote 4)
--3-----------1---------LADN31------------LA1DN31
--3-----------1---------LA1DZ31----------LA1DZ31 (See Footnote 5)
--1-----------3---------LADN13------------LA1DN13
--4-----------0---------LADN40------------LA1DN40
--4-----------0---------LA1DZ40-----------LA1DZ40 (See Footnote 6)
--0-----------4---------LADN04------------LA1DN04




Front Mounting; maximum of 1 block per contactor: For use with D2 Series 25 amp through 80 amp contactors and TeSys Series 40 amp through 80 amp only.

N.O.-------N.C.-----TeSys P/N--------Pre-TeSys P/N
--1-----------0--------LADN10----------LA1DN10
--0-----------1--------LADN01----------LA1DN01

Side Mounting; maximum of 1 block on each side for D2 Series and Tesys Series 40 through 80 amp contactors. Tesys 9 through 32, 115, and 150 amps contactors will accept 1 block and is limited to left side only. (*) DC control devices will not accept side mount auxiliaries.
(*) DC control exceptions that will accept one left side mounted auxiliary: LC1D115 & LC1D150.

N.O.-------N.C.-----TeSys P/N--------Pre-TeSys P/N
--1-----------1--------LAD8N11----------LA8DN11
--2-----------0--------LAD8N20----------LA8DN20
--0-----------2--------LAD8N02----------N/A

Footnotes:
{1.EN_US} EN50 012 Machine Tool Terminal Markings
{2.EN_US} (2) NO Sealed Dust Tight Contacts
{3.EN_US} Gold Flash Contacts
{4.EN_US} (1) NO & (1) NC Standard and (1) NO & (1) NC Make Before Break
{5.EN_US} (2) NO Dust Tight Contacts & (1) NO & (1) NC Standard Contacts
{6.EN_US} (2) NO Dust Tight Contacts & (2) NO Standard Contacts

What is the replacement enclosure for a 9013FSW or 9013FYW pressure switch?

Issue:
Replacement NEMA 3R enclosure for a 9013FSW or 9013FYW.

Product Line: 
Pressure, Vacuum, and Float Switches

Environment:
9013 Type F Pressure Switches

Resolution:
These are not available as a repair part.  Replace the entire switch.

What are the 9013FHG pressure switch contacts rated at?

Issue:
Contact Rating of 9013F Pressure Switches

Product Line: 
Pressure, vacuum and Float Switches 

Environment:
9013 Type F Pressure Switch 

Resolution:
Those contacts have a control circuit rating of A600.
They are DC rated at 1/4 HP at 115V and 230V (Except form M4)
They are Single Phase AC rated 1 1/2 HP at 115V, 2 HP at 230V
They are Polyphase rated 2 HP at 115V, 3 HP at 230V, and 1 HP at 460/575V.

This also applies to the 9013 FHG2, 9, 12, 13, 44, 49 9013 FSG, and FSW.

Is the 9013F compatible with Skydrol?

Issue:
Is the 9013F compatible with Skydrol?

Product Line:
Pressure switches

Environment:
9013F

Cause:
Material comparability

Resolution:
It is not recommended for Skydrol.  Nitrile is the standard material used in diaphragm for the 9013F devices. The 9012G has an option to use ethylene propylene, form Q3, for the diaphragm.

Note that 9012G switches are control devices and cannot support inductive loads directly, but require an interposing contactor.

What does the form B4 stand for on a 9012 pressure switch?

Issue:
9012GAW4 B4: What does the B4 stand for?

Product Line:
Pressure Switches

Environment:
Class 9012

Cause:
Product features and nomenclature.

Resolution:
The form B4 is no longer available for the above pressure switch. However, it was for a detachable bottom conduit hub.

What is the temperature rating of a 9013FSG2J20? Will it work in hot water at 140 F?

 
Issue: 
What is the temperature rating of a 9013FSG2J20? Will it  work in hot water at 140 F?

Product Line:
Pressure Switches

Environment:
Pressure switches commercialized in the US

Cause:
What is the temperature rating of a 9013FSG2J20? Will it  work in hot water at 140 F?
 
Resolution:
The Media temperature for all 9013 F & G switches is minimum -30C (-22F) and maximum 125C (257F).

The ambient temperature is a minimum of -30C (-22F) and a maximum of 70C (158F).

What are the cross bar and lifting hook part numbers for Masterpact NW breakers?

Issue:
How do I lift a Masterpact NW breaker?  What are the cross bar and lifting hook part numbers?

Product Line:
Masterpact NW

Resolution:
You will need a cross bar depending on the frame, a kit of lifting hooks, and a lifting truck or hoist provided by yourself:
Crossbar for W-Frame Circuit Breaker or Cradle - S48900
Crossbar for Y-Frame Circuit Breaker or Cradle - S48901
Set of Two Lifting Hooks - S48906

9013 Type F pressure switch came with Form X - can he bypass that pressure release valve?

Issue:
Type F pressure switch came with Form X - can he bypass that pressure release valve

Product Line: 
Pressure, Vacuum, and Float Switches

Environment:
9013 Type F Pressure Switches

Resolution:
Just do not hook anything to it - Form X is just a mechanical bleed valve.

9013 Type G pressure switch: What is the Factory setting tolerance?

Issue:
Factory setting tolerance for type G pressure switch

Product Line: 
Pressure, Vacuum, and Float Switches

Environment:
Class 9013 Type G Pressure Switches

Resolution:
Factory setting tolerance is  + 4 psi.

What are the replacement contacts and diaphragm part numbers for a 9013FHG pressure switch?

Issue:
9013FHG pressure switch repair kit

Product Line:
Commercial Pressure Switches

Environment:
Type F—Pumptrol™ Water Pump Pressure Switches

Resolution:
For standard (non-special) devices:
  • Types FHG2 thru 19 order 9998 PC241.
  • Types FHG22 thru 39 order 9998 PC242.
  • Types FHG42 thru49 order 9998 PC241.
  • Types FHG52 thru 59 order 9998 PC242.
Note: the diaphragm comes with the replacement contacts.

What is the replacement contact/diaphragm kit # for 9013GHG2?

Issue:
replacement contact/diaphragm kit for 9013GHG2

Product Line: 
Pressure, Vaccum and Float Switches

Environment:
9013 Float Switches

Resolution:
9998PC205 is the contacts only for All 9013 GHG except with Forms H( NO and NC) and R (Reverse action). ONLY means alone and that no other parts are included.

The Diaphragm assy would be part number 9998PC208. The diaphram is a mechanical acutating mechanism which has no electrical components in it as it is shipped.