Acti9, Residual current breaker with overcurrent protection (RCBO), iC60N RCBO, 1P + Ns, 16A, 30mA, A type, 6000A

Home ProductsCircuit ProtectionActi 9Residual current breaker with overcurrent protection (RCBO)

Acti9, Residual current breaker with overcurrent protection (RCBO), iC60N RCBO, 1P + Ns, 16A, 30mA, A type, 6000A

Item Number: A9D61816

Datasheet

Product Dimensions

Width icon

Width18 mm

Height icon

Height110 mm

Depth icon

Depth77.5 mm

Barcode

Qty UoM EAN Colour
-
-
-

Specifications

Design

Range

Acti9

Product or component type

residual current breaker with overcurrent protection (RCBO)

Physical

[in] rated current

16 A at 50 °C

[ue] rated operational voltage

230/240 V AC 50/60 Hz

Control type

toggle

Local signalling

ON/OFF indication

Mounting mode

clip-on

Mounting support

DIN rail

Height

110 mm

Width

18 mm

Depth

77.5 mm

Net weight

205 g

Mechanical durability

20000 cycles

Electrical durability

5000 cycles

Connections - terminals

screw clamp terminal (top) 1-25 mm² rigid without cable end|screw clamp terminal (top) 1-16 mm² flexible|screw clamp terminal (bottom) 1-16 mm² rigid without cable end|screw clamp terminal (bottom) 1-10 mm² flexible

Wire stripping length

power circuit: 13 mm for bottom connection|power circuit: 14 mm for top connection

Standards

IEC 61009-2-2|IEC 61009-1|AS/NZS 61009.1

Ip degree of protection

IP20

Relative humidity

95 % at 55 °C

Ambient air temperature for operation

-15...60 °C

Ambient air temperature for storage

-40...85 °C

Reach regulation

Reference contains Substances of Very High Concern above the threshold

Eu rohs directive

Not compliant

China rohs regulation

Product out of China RoHS scope. Substance declaration for your information

Environmental disclosure

ENVPEP121008EN

Circularity profile

N/A

Others

Package 1 bare product quantity

1

Circuit breaker application

distribution

Product name

Acti9 iC60 RCBO

Device short name

iC60N RCBO

Poles description

1P + Ns

Earthing system

TN

Curve code

C

Earth-leakage sensitivity

30 mA

Breaking capacity

6000 A Icn at 230/240 V AC 50/60 Hz

Neutral position

left

Number of protected poles

1

Device location in system

outgoer

Network frequency

50 Hz

Network type

AC

Trip unit technology

thermal-magnetic

Breaking capacity code

N

Residual current tripping technology

voltage dependent

Earth-leakage protection time delay

instantaneous

Earth-leakage protection class

type A

[icw] rated short-time withstand current

Icw: 250 A during 8/20 µs impulse withstand

[ics] rated service breaking capacity

6000 A at 230/240 V AC 50/60 Hz

Limitation class

3

[ui] rated insulation voltage

400 V AC 50/60 Hz

[uimp] rated impulse withstand voltage

4 kV

Surge current

250 A

Suitability for isolation

yes

Contact position indicator

yes

Comb busbar and distribution block compatibility

NO

9 mm pitches

2

Provision for padlocking

padlockable with padlock Ø 4 mm

Locking options description

ON/OFF locking facilities

Tightening torque

power circuit: 3.5...3.5 N.m top|power circuit: 2 N.m bottom

Earth-leakage protection

integrated

Tropicalisation

2

Unit type of package 1

PCE

Number of units in package 1

1

Package 1 height

2.6 cm

Package 1 width

2.8 cm

Package 1 length

11.2 cm

Package 1 weight

220 g

Unit type of package 2

BB1

Number of units in package 2

34

Package 2 height

154 cm

Package 2 width

290 cm

Package 2 length

398 cm

Package 2 weight

7.798 kg

Take-back

No

Product contributes to saved and avoided emissions

No

Removable battery

N/A

Carbon footprint (kg.eq.co2 per cr, total life cycle)

21.2041586299