Acti9 iC60H3 Residual current breaker with overcurrent protection (RCBO) 3P+Ns, C Curve, 16A, 30mA, A type, 10000A

Home ProductsCircuit ProtectionActi 9Residual current breaker with overcurrent protection (RCBO)

Acti9 iC60H3 Residual current breaker with overcurrent protection (RCBO) 3P+Ns, C Curve, 16A, 30mA, A type, 10000A

Item Number: A9DC1916

Datasheet

Product Dimensions

Width icon

Width54 mm

Height icon

Height112 mm

Depth icon

Depth77.2 mm

Barcode

Qty UoM EAN Colour
-
-
-

Specifications

Design

Range

Acti9

Product or component type

residual current breaker with overcurrent protection (RCBO)

Physical

Ambient air temperature for operation

-5...60 °C

Ambient air temperature for storage

-25...70 °C

Standards

AS/NZS 61009.1|IEC 61009-1|IEC 61009-2-2

Ip degree of protection

IP20

Relative humidity

95 % at 55 °C

[in] rated current

16 A at 30 °C

[ue] rated operational voltage

400/415 V

Control type

toggle

Local signalling

ON/OFF indication

Mounting mode

clip-on

Mounting support

DIN rail|chassis

Height

112 mm

Width

54 mm

Depth

77.2 mm

Net weight

462 g

Mechanical durability

20000 cycles

Electrical durability

5000 cycles

Connections - terminals

screw clamp terminal (top) 1-25 mm² rigid without cable end|screw clamp terminal (top) 1-16 mm² flexible

Wire stripping length

power circuit: 11 mm for bottom connection|power circuit: 14 mm for top connection

Reach regulation

Free of Substances of Very High Concern above the threshold

Reach free of svhc

Yes

Eu rohs directive

Compliant

Rohs exemption information

Yes

China rohs regulation

 Pro-active China RoHS declaration (out of China RoHS legal scope)

Environmental disclosure

ENVPEP2308033EN

Circularity profile

ENVEOLI2308033EN

Others

Commercial status history

SESA602958 | Sun Oct 29 17:29:00 EDT 2023 | From Unitary Local | From 06 to 08

Package 1 bare product quantity

1

Package 2 bare product quantity

16

Tropicalisation

2

Circuit breaker application

distribution

Product name

Acti9 iC60 RCBO

Device short name

iC60H3 RCBO

Poles description

3P + Ns

Earthing system

TN

Curve code

C

Earth-leakage sensitivity

30 mA

Breaking capacity

10000 A Icn at 400/415 V

Neutral position

left

Number of protected poles

3

Device location in system

outgoer

Network frequency

50/60 Hz

Network type

AC

Trip unit technology

thermal-magnetic

Residual current tripping technology

voltage dependent

Earth-leakage protection time delay

instantaneous

Earth-leakage protection class

type A

[icw] rated short-time withstand current

Icw: 250 A during 8/20 µs impulse withstand

[ics] rated service breaking capacity

7500 A

Limitation class

3

[ui] rated insulation voltage

500 V

[uimp] rated impulse withstand voltage

4 kV

Surge current

250 A

Suitability for isolation

yes conforming to IEC 61009-1

Comb busbar and distribution block compatibility

YES

9 mm pitches

6

Provision for padlocking

padlockable with padlock Ø 4 mm|lead seal

Locking options description

ON/OFF locking facilities

Tightening torque

power circuit: 2.5...2.5 N.m top|power circuit: 2.5...2.5 N.m bottom

Earth-leakage protection

integrated

Test button operating voltage

260...457 V

Operating voltage earthleakage protection

150...457 V

Grid distance

45 mm

Locking options description

handle sealable with cable diameter 1.4mm in OFF or ON position

Unit type of package 1

PCE

Number of units in package 1

1

Package 1 height

12.7 cm

Package 1 width

6.6 cm

Package 1 length

9 cm

Package 1 weight

539 g

Unit type of package 2

S02

Number of units in package 2

16

Package 2 height

15 cm

Package 2 width

30 cm

Package 2 length

40 cm

Package 2 weight

9.376 kg

Packaging made with recycled cardboard

Yes

Packaging without single use plastic

Yes

Take-back

No

Take-back

No

Product contributes to saved and avoided emissions

No

Removable battery

N/A

Carbon footprint (kg.eq.co2 per cr, total life cycle)

7.644160878
Show all specifications