Acti9, Miniature circuit breaker (MCB), iC60N Disbo, 2P, 40A, C curve, 6000A (IEC/EN 60898-1), 10kA (IEC/EN 60947-2)

Home ProductsCircuit ProtectionActi 9Miniature circuit breaker (MCB)

Acti9, Miniature circuit breaker (MCB), iC60N Disbo, 2P, 40A, C curve, 6000A (IEC/EN 60898-1), 10kA (IEC/EN 60947-2)

Item Number: A9F44240

Datasheet

Product Dimensions

Width icon

Width36 mm

Height icon

Height85 mm

Depth icon

Depth78.5 mm

Barcode

Qty UoM EAN Colour
-
-
-

Specifications

Design

Range

Acti9

Range of product

Acti9

Product or component type

miniature circuit-breaker

Physical

[in] rated current

40 A

[ue] rated operational voltage

400 V AC 50/60 Hz

Control type

toggle

Local signalling

trip indicator

Mounting mode

clip-on

Mounting support

rail

Height

85 mm

Width

36 mm

Depth

78.5 mm

Net weight

0.25 kg

Mechanical durability

20000 cycles

Electrical durability

10000 cycles

Connections - terminals

single terminal (top or bottom) 1-35 mm² rigid|single terminal (top or bottom) 1-25 mm² flexible

Wire stripping length

14 mm for top or bottom connection

Standards

EN/IEC 60898-1|EN/IEC 60947-2

Ip degree of protection

IP20 conforming to IEC 60529

Relative humidity

95 % at 55 °C

Ambient air temperature for operation

-35...70 °C

Ambient air temperature for storage

-40...85 °C

Reach regulation

Reference contains Substances of Very High Concern above the threshold

Eu rohs directive

Compliant

Toxic heavy metal free

Yes

Mercury free

Yes

Rohs exemption information

Yes

China rohs regulation

 Pro-active China RoHS declaration (out of China RoHS legal scope)

Environmental disclosure

ENVPEP1705002EN

Circularity profile

N/A

Others

Package 1 bare product quantity

1

Package 2 bare product quantity

6

Package 3 bare product quantity

66

Packaging without single use plastic

Yes

Product name

Disbo iC60

Device short name

IC60N

Poles description

2P

Number of protected poles

2

Network type

AC/DC

Trip unit technology

thermal-magnetic

Curve code

C

Breaking capacity code

N

Breaking capacity

10 kA Icu at <= 125 V DC conforming to EN/IEC 60947-2|6000 A Icn at 415 V AC 50/60 Hz conforming to EN/IEC 60898-1|36 kA Icu at 12...133 V AC 50/60 Hz conforming to EN/IEC 60947-2|20 kA Icu at 220...240 V AC 50/60 Hz conforming to EN/IEC 60947-2|10 kA Icu at 380...415 V AC 50/60 Hz conforming to EN/IEC 60947-2|6 kA Icu at 440 V AC 50/60 Hz conforming to EN/IEC 60947-2

Utilisation category

category A conforming to EN/IEC 60947-2

Network frequency

50/60 Hz

Magnetic tripping limit

8 x In +/- 20 %

[ics] rated service breaking capacity

27 kA 75 % conforming to EN/IEC 60947-2 - 12...133 V AC 50/60 Hz|15 kA 75 % conforming to EN/IEC 60947-2 - 220...240 V AC 50/60 Hz|7.5 kA 75 % conforming to EN/IEC 60947-2 - 380...415 V AC 50/60 Hz|4.5 kA 75 % conforming to EN/IEC 60947-2 - 440 V AC 50/60 Hz|6000 A 100 % conforming to EN/IEC 60898-1 - 415 V AC 50/60 Hz|6 kA 100 % conforming to EN/IEC 60947-2 - 100...133 V DC

Limitation class

3 conforming to EN/IEC 60947-2

[ui] rated insulation voltage

500 V AC 50/60 Hz

[uimp] rated impulse withstand voltage

6 kV conforming to EN/IEC 60947-2

Contact position indicator

yes

Connection pitch

18 mm between phases

9 mm pitches

4

Total power losses

7.2 W

Power losses per pole

3.6 W

Provision for padlocking

padlockable

Tightening torque

3.5...3.5 N.m top or bottom

Earth-leakage protection

separate block

Compatibility code

iC60

Pollution degree

3 conforming to EN/IEC 60947-2

Tropicalisation

2 conforming to IEC 60068-1

Unit type of package 1

PCE

Number of units in package 1

1

Package 1 height

3.700 cm

Package 1 width

7.300 cm

Package 1 length

8.900 cm

Package 1 weight

238.000 g

Unit type of package 2

BB1

Number of units in package 2

6

Package 2 height

8.500 cm

Package 2 width

9.800 cm

Package 2 length

22.000 cm

Package 2 weight

1.491 kg

Unit type of package 3

S03

Number of units in package 3

66

Package 3 height

30.000 cm

Package 3 width

30.000 cm

Package 3 length

40.000 cm

Package 3 weight

17.000 kg

Scip number

26ff71d1-98cf-4280-8725-455b9a6b2fb9

Weee

The product must be disposed on European Union markets following specific waste collection and never end up in rubbish bins

Halogen content performance

Halogen free product

Halogen content performance

Halogen free product

Take-back

No

Product contributes to saved and avoided emissions

No

Removable battery

N/A

Carbon footprint (kg.eq.co2 per cr, total life cycle)

41.134444188101874
Show all specifications

Documents & downloads

hide show
Filter items
  • All

  • CAD Files and Packs

  • Environmental Disclosure

  • Certificates (MSDS)

  • Declaration of Conformity

Frequently Asked Questions

hide show

Can I use the 2P iC60 (N or H) MCB for 400V application (e.g. measuring 400V across phase to Neutral)?

Issue:

Can use the 2P iC60 (N or H) MCB for 400V application measuring 400V across phase to Neutral?

Product Line:

Acti 9

Environment:

iC60 (N or H)

Resolution:

Yes, MCBs Acti9 iC60N/H 2P can be used under Ue (Ph/N) or (Ph/Ph)=400Vac applications.
You can refer to breaking capacities declared in catalogue pages for Ue=380-415Vac (e.g Icu=10kA for iC60N 2P C 40A including ref.A9F44240).