Acti9, Miniature circuit breaker (MCB), C60H-DC, 1P, 25A, C curve, 6kA (IEC/EN 60947-2)

Home ProductsCircuit ProtectionActi 9Miniature circuit breaker (MCB)

Acti9, Miniature circuit breaker (MCB), C60H-DC, 1P, 25A, C curve, 6kA (IEC/EN 60947-2)

Item Number: A9N61513

Datasheet

Barcode

Qty UoM EAN Colour
-
-
-

Specifications

Design

Range of product

C60

Range

Acti9

Product or component type

miniature circuit-breaker

Device application

distribution

Product compatibility

C60 accessories|C60 auxiliary

Market segment

small commercial|residential

Warranty

18 months

Physical

[in] rated current

25 A at 25 °C

Standards

EN 60947-2|IEC 60947-2

[ue] rated operational voltage

250 V DC

Control type

toggle

Local signalling

ON/OFF indication

Mounting mode

fixed

Mounting support

35 mm symmetrical DIN rail

Net weight

0.128 kg

Mechanical durability

20000 cycles

Electrical durability

3000 cycles L/R = 2 ms

Ambient air temperature for operation

-25...70 °C

Ambient air temperature for storage

-40...85 °C

Reach regulation

Reference contains Substances of Very High Concern above the threshold

Eu rohs directive

Compliant

Toxic heavy metal free

Yes

Mercury free

Yes

China rohs regulation

 Pro-active China RoHS declaration (out of China RoHS legal scope)

Rohs exemption information

Yes

Environmental disclosure

ENVPEP2308050EN

Circularity profile

N/A

Others

Package 1 bare product quantity

1

Product name

Acti9 C60H-DC

Device short name

C60H-DC

Poles description

1P

Number of protected poles

1

Network type

DC

Trip unit technology

thermal-magnetic

Curve code

C

Breaking capacity code

H

Breaking capacity

10 kA Icu at 220 V DC conforming to EN 60947-2|10 kA Icu at 220 V DC conforming to IEC 60947-2|6 kA Icu at 250 V DC conforming to EN 60947-2|6 kA Icu at 250 V DC conforming to IEC 60947-2|20 kA Icu at 110 V DC conforming to EN 60947-2|20 kA Icu at 110 V DC conforming to IEC 60947-2

Utilisation category

category A conforming to EN 60947-2|category A conforming to IEC 60947-2

Suitability for isolation

yes conforming to IEC 60947-2|yes conforming to EN 60947-2

Network frequency

50/60 Hz

[ics] rated service breaking capacity

15 kA 75 % conforming to EN 60947-2 - 110 V DC|15 kA 75 % conforming to IEC 60947-2 - 110 V DC|4.5 kA 75 % conforming to EN 60947-2 - 250 V DC|4.5 kA 75 % conforming to IEC 60947-2 - 250 V DC|7.5 kA 75 % conforming to EN 60947-2 - 220 V DC|7.5 kA 75 % conforming to IEC 60947-2 - 220 V DC

[ui] rated insulation voltage

500 V DC conforming to IEC 60947-2|500 V DC conforming to EN 60947-2

[uimp] rated impulse withstand voltage

6 kV conforming to EN 60947-2|6 kV conforming to IEC 60947-2

Contact position indicator

yes

Comb busbar and distribution block compatibility

top or bottom: standard

9 mm pitches

2

Total power losses

3.1 W

Power losses per pole

3.1 W

Provision for padlocking

padlockable

Locking options description

in position O

Tightening torque

power circuit: 2.5...2.5 N.m top or bottom

Earth-leakage protection

without

Compatibility code

C60H-DC

Pollution degree

3 conforming to EN 60947-2|3 conforming to IEC 60947-2

Overvoltage category

IV

Tropicalisation

2 conforming to IEC 60068-2

Operating altitude

2000 m

Unit type of package 1

PCE

Number of units in package 1

1

Package 1 height

7.3 cm

Package 1 width

1.8 cm

Package 1 length

8.5 cm

Package 1 weight

121.0 g

Unit type of package 2

BB1

Number of units in package 2

12

Package 2 height

2.85 cm

Package 2 width

30.0 cm

Package 2 length

20.0 cm

Package 2 weight

1.421 kg

Unit type of package 3

S03

Number of units in package 3

144

Package 3 height

30.0 cm

Package 3 width

30.0 cm

Package 3 length

40.0 cm

Package 3 weight

17.666 kg

Scip number

a5974528-db7a-4dab-baff-e3d40953a6f2

Bvb url

https://byggvarubedomningen.se/

Bvb

Accepted

Take-back

No

Product contributes to saved and avoided emissions

No

Removable battery

N/A

Carbon footprint (kg.eq.co2 per cr, total life cycle)

17.84341538631179
Show all specifications

Frequently Asked Questions

hide show

Can A9N61512 iC60H DC breaker be fed from top

No, the breaker is Polarized and can only be Fed from Bottom
image.pngimage.png
It will be the same for all iC0H DC single pole breakers:
C60H-DC Rating (In) Reference C curve 1P
1A A9N61501
2A A9N61502
4A A9N61504
6A A9N61506
10A A9N61508  
16A A9N61511
20A A9N61512
25A A9N61513
32A A9N61515
40A A9N61517
50A A9N61518
63A A9N61519