Acti9, Miniature circuit breaker (MCB), C120H, 4P, 125A, B curve, 15000A (IEC/EN 60898-1), 15kA (IEC/EN 60947-2)

Home ProductsCircuit ProtectionActi 9Miniature circuit breaker (MCB)

Acti9, Miniature circuit breaker (MCB), C120H, 4P, 125A, B curve, 15000A (IEC/EN 60898-1), 15kA (IEC/EN 60947-2)

Item Number: A9N18437

Datasheet

Product Dimensions

Width icon

Width108 mm

Height icon

Height81 mm

Depth icon

Depth73 mm

Barcode

Qty UoM EAN Colour
-
-
-

Specifications

Design

Range of product

C120

Range

Acti9

Product or component type

miniature circuit-breaker

Device application

distribution

Market segment

small commercial|residential

Warranty

18 months

Physical

[in] rated current

125 A at 30 °C

Standards

EN/IEC 60947-2|EN/IEC 60898-1

Product certifications

EAC

[ue] rated operational voltage

380...415 V AC 50/60 Hz|<= 500 V DC|220...240 V AC 50/60 Hz|440 V AC 50/60 Hz|230...400 V AC 50/60 Hz

Control type

toggle

Local signalling

ON/OFF indication

Mounting mode

clip-on

Mounting support

35 mm symmetrical DIN rail

Height

81 mm

Depth

73 mm

Width

108 mm

Net weight

0.82 kg

Mechanical durability

20000 cycles

Electrical durability

5000 cycles conforming to IEC 60947-2

Connections - terminals

tunnel type terminals1-50 mm² rigid|tunnel type terminals1.5-35 mm² flexible

Wire stripping length

15 mm

Ip degree of protection

IP20 conforming to IEC 60529

Relative humidity

95 % at 55 °C

Ambient air temperature for operation

-30...60 °C

Ambient air temperature for storage

-40...70 °C

Reach regulation

Reference contains Substances of Very High Concern above the threshold

Eu rohs directive

Compliant

Toxic heavy metal free

Yes

Mercury free

Yes

China rohs regulation

X

Rohs exemption information

Yes

Environmental disclosure

ENVPEP121230EN

Circularity profile

N/A

Others

Package 1 bare product quantity

1

Product name

C120

Device short name

C120H

Poles description

4P

Number of protected poles

4

Network type

AC

Trip unit technology

thermal-magnetic

Curve code

B

Breaking capacity code

H

Breaking capacity

15000 A Icn at 230...400 V AC 50/60 Hz conforming to EN/IEC 60898-1|10 kA Icu at 440 V AC 50/60 Hz conforming to EN/IEC 60947-2|15 kA Icu at 380...415 V AC 50/60 Hz conforming to EN/IEC 60947-2|30 kA Icu at 220...240 V AC 50/60 Hz conforming to EN/IEC 60947-2|15 kA Icu at <= 500 V DC conforming to EN/IEC 60947-2

Suitability for isolation

yes conforming to IEC 60947-2

Network frequency

50/60 Hz

Magnetic tripping limit

3...5 x In

[ics] rated service breaking capacity

7500 A 50 % conforming to EN/IEC 60898-1 - 230...400 V AC 50/60 Hz|5 kA 50 % conforming to EN/IEC 60947-2 - 440 V AC 50/60 Hz|15 kA 50 % conforming to EN/IEC 60947-2 - 220...240 V AC 50/60 Hz|7.5 kA 50 % conforming to EN/IEC 60947-2 - 380...415 V AC 50/60 Hz|15 kA 100 % conforming to EN/IEC 60947-2 - <= 500 V DC

Limitation class

3 conforming to EN/IEC 60947-2

[ui] rated insulation voltage

500 V AC 50/60 Hz conforming to EN/IEC 60947-2

[uimp] rated impulse withstand voltage

6 kV conforming to EN/IEC 60947-2

Contact position indicator

yes

Connection pitch

27 mm between phases

Comb busbar and distribution block compatibility

NO

9 mm pitches

12

Total power losses

12.3 W

Power losses per pole

4.1 W

Tightening torque

3.5...3.5 N.m

Earth-leakage protection

separate block

Compatibility code

C120

Pollution degree

3 conforming to IEC 60947-2

Overvoltage category

IV

Tropicalisation

2 conforming to IEC 60068-1

Operating altitude

2000 m

Unit type of package 1

PCE

Number of units in package 1

1

Package 1 height

7.5 cm

Package 1 width

8.6 cm

Package 1 length

10.8 cm

Package 1 weight

776 g

Unit type of package 2

BB1

Number of units in package 2

3

Package 2 height

8.7 cm

Package 2 width

33.9 cm

Package 2 length

9.9 cm

Package 2 weight

2.402 kg

Unit type of package 3

S03

Number of units in package 3

18

Package 3 height

30 cm

Package 3 width

30 cm

Package 3 length

40 cm

Package 3 weight

14.899 kg

Bvb url

https://byggvarubedomningen.se/

Bvb

Accepted

Weee

The product must be disposed on European Union markets following specific waste collection and never end up in rubbish bins

Take-back

No

Product contributes to saved and avoided emissions

No

Removable battery

N/A

Carbon footprint (kg.eq.co2 per cr, total life cycle)

73.03471042
Show all specifications