Acti9, Impulse relay, iTLI, 2P, 1NO+1NC, 16A, coil 110 VDC, 230...240 VAC 50/60Hz

Acti9, Impulse relay, iTLI, 2P, 1NO+1NC, 16A, coil 110 VDC, 230...240 VAC 50/60Hz

Item Number: A9C30815

Datasheet

Product Dimensions

Width icon

Width18 mm

Height icon

Height84 mm

Depth icon

Depth60 mm

Barcode

Qty UoM EAN Colour
-
-
-

Specifications

Design

Range of product

iTL

Range

Acti9

Product or component type

impulse relay

Device application

changeover relay

Market segment

small commercial|residential

Warranty

18 months

Physical

[in] rated current

16 A

[ue] rated operational voltage

250 V AC 50/60 Hz

Control type

coil deconnection|remote and manual control

Control signal type

impulse

Remote control type

illuminated push-button 3 mA

Local signalling

ON/OFF indication

Mounting mode

fixed

Mounting support

DIN rail

Height

84 mm

Width

18 mm

Depth

60 mm

Electrical durability

AC-21: 200000 cycles|AC-22: 100000 cycles

Connections - terminals

control circuit: tunnel type terminals 1 cable(s) 0.5-4 mm² rigid|control circuit: tunnel type terminals 1 cable(s) 0.5-4 mm² rigid with cable end|control circuit: tunnel type terminals 1 cable(s) 1-4 mm² flexible|control circuit: tunnel type terminals 1 cable(s) 1-4 mm² flexible with ferrule|power circuit: tunnel type terminals 1 cable(s) 1.5-4 mm² rigid|power circuit: tunnel type terminals 1 cable(s) 1.5-4 mm² rigid with cable end|power circuit: tunnel type terminals 1 cable(s) 1.5-4 mm² flexible|power circuit: tunnel type terminals 1 cable(s) 1.5-4 mm² flexible with ferrule

Wire stripping length

11 mm

Range compatibility

Acti 9 iATEt|Acti 9 iATL4|Acti 9 iATLc|Acti 9 iATLc+s|Acti 9 iATLm|Acti 9 iATLs|Acti 9 iATLz|Acti 9 iETL iTL 16|Acti 9 iATLc+c|Acti 9 iATL24

Standards

EN 669-1|EN 669-2-2

Product certifications

CCC|GOST

Ip degree of protection

IP20 conforming to IEC 60529 (on opening)|IP40 conforming to IEC 60529 (in enclosure)

Relative humidity

95 % at 55 °C

Ambient air temperature for operation

-20...50 °C

Ambient air temperature for storage

-40...70 °C

Reach regulation

Reference contains Substances of Very High Concern above the threshold

Eu rohs directive

Compliant

Toxic heavy metal free

Yes

Mercury free

Yes

Rohs exemption information

Yes

China rohs regulation

X

Environmental disclosure

ENVPEP2311015EN

Circularity profile

N/A

Others

Package 1 bare product quantity

1

Package 2 bare product quantity

12

Package 3 bare product quantity

144

Product name

Acti9 iTL

Device short name

iTLi

Poles description

2P

Pole contact composition

1 NO + 1 NC

Network type

AC

[uc] control circuit voltage

230...240 V AC 50/60 Hz|110 V DC

Network frequency

50/60 Hz

Switching frequency

5 switching operations/minute|100 switching operations/day

Impulse duration

50 ms...1 s

9 mm pitches

2

Total power losses

0.6 W

Power losses per pole

0.6 W

Tightening torque

1 N.m

Compatibility code

iTLi

Quality labels

CEBEC|NF|IMQ|KEMA|VDE

Noise level

60 dB

Pollution degree

3

Tropicalisation

2

Unit type of package 1

PCE

Number of units in package 1

1

Package 1 height

7.500 cm

Package 1 width

1.700 cm

Package 1 length

8.500 cm

Package 1 weight

112.000 g

Unit type of package 2

BB1

Number of units in package 2

12

Package 2 height

8.500 cm

Package 2 width

9.300 cm

Package 2 length

22.300 cm

Package 2 weight

1.398 kg

Unit type of package 3

S03

Number of units in package 3

144

Package 3 height

30.000 cm

Package 3 width

30.000 cm

Package 3 length

40.000 cm

Package 3 weight

17.300 kg

Scip number

6763a476-30bc-4d05-a4bb-93f8d65c3771

Bvb url

https://byggvarubedomningen.se/

Bvb

Accepted

Weee

The product must be disposed on European Union markets following specific waste collection and never end up in rubbish bins

Halogen content performance

Halogen free plastic parts product

Take-back

No

Product contributes to saved and avoided emissions

No

Removable battery

N/A

Carbon footprint (kg.eq.co2 per cr, total life cycle)

6.350873609
Show all specifications