Acti9, IEM3565 energy meter, BACnet - 1 DI - 1 DO - multi-tariff - Rogowski coil

Acti9, IEM3565 energy meter, BACnet - 1 DI - 1 DO - multi-tariff - Rogowski coil

Item Number: A9MEM3565

Datasheet

Product Dimensions

Width icon

Width90 mm

Height icon

Height87 mm

Depth icon

Depth69 mm

Barcode

Qty UoM EAN Colour
-
-
-

Specifications

Design

Range

Acti9

Product or component type

energy meter

Market segment

buildings small building cost management: billing: main incomer|buildings small building cost management: billing: sub feeder|buildings small building cost management: billing: panelboard|buildings medium building cost management: billing: main incomer|buildings medium building cost management: billing: sub feeder|buildings medium building cost management: billing: panelboard|buildings large building cost management: billing: main incomer|buildings large building cost management: billing: sub feeder|buildings large building cost management: billing: panelboard|buildings multi-site cost management: billing: main incomer|buildings multi-site cost management: billing: sub feeder|buildings multi-site cost management: billing: panelboard|data center cost management: billing|healthcare cost management: billing|industry cost management: billing|buildings small building cost management: cost allocation: main incomer|buildings small building cost management: cost allocation: sub feeder|buildings small building cost management: cost allocation: panelboard|buildings medium building cost management: cost allocation: main incomer|buildings medium building cost management: cost allocation: sub feeder|buildings medium building cost management: cost allocation: panelboard|buildings large building cost management: cost allocation: main incomer|buildings large building cost management: cost allocation: sub feeder|buildings large building cost management: cost allocation: panelboard|buildings multi-site cost management: cost allocation: main incomer|buildings multi-site cost management: cost allocation: sub feeder|buildings multi-site cost management: cost allocation: panelboard|data center cost management: cost allocation|healthcare cost management: cost allocation|industry cost management: cost allocation

Device application

sub billing|partial meter|multi-tariff

Physical

Rated voltage

100...277 V +/- 20 %|173...480 V +/- 20 %

Communication port protocol

BACnet at 9.6, 19.2, 38.4, 57.6, 76.8 kbauds

Local signalling

green indicator light: power ON|yellow flashing LED: accuracy checking| alarm: overload

Mounting mode

clip-on

Mounting support

DIN rail

Connections - terminals

current circuit: screw terminals 6-6 mm² cable(s) |voltage circuit: screw terminals 2.5-2.5 mm² cable(s) |input/output circuit: screw terminals 1.5-1.5 mm² cable(s) |communication: screw terminals 2.5-2.5 mm² cable(s)

Wire stripping length

input/output circuit: 6 mm|voltage circuit: 8 mm|current circuit: 8 mm|communication: 7 mm

Standards

BS EN 61326-1|IEC 61326-1|EN 61326-1|BS EN 61010-1:2010|EN 61010-1:2010|IEC 61010-1:2010|UL 61010-1:2010|BS EN 61010-2-30|IEC 61010-2-30|EN 61010-2-30|UL 61010-2-30|ANSI C12.20

Product certifications

CE conforming to IEC 61010-1 (safety)|CE conforming to EN 61557-12 (power monitor)|CE conforming to EN/IEC 61326-1 (EMC)|UKCA conforming to BS EN 61010-1 (safety)|UKCA conforming to BS EN 61557-12 (power monitor)|UKCA conforming to BS EN 61326-1 (EMC)|cULus conforming to UL 61010-1 (safety)|cULus conforming to EN 61010-1 (safety)|KZ|RCM

Ip degree of protection

IP40 front panel: conforming to IEC 60529|IP20 body: conforming to IEC 60529

Ik degree of protection

IK08

Relative humidity

5...95 % at 36 °C

Ambient air temperature for operation

-25...70 °C - IEC

Ambient air temperature for storage

-40...85 °C

Width

90 mm

Height

87 mm

Depth

69 mm

Reach regulation

Reference contains Substances of Very High Concern above the threshold

Eu rohs directive

Compliant with Exemptions

Mercury free

Yes

Rohs exemption information

Yes

China rohs regulation

X

Environmental disclosure

ENVPEP111276EN

Circularity profile

ENVEOLI111261EN_V1

California proposition 65

WARNING: Cancer and Reproductive Harm - www.P65Warnings.ca.gov

Others

Package 2 bare product quantity

30

Package 3 bare product quantity

240

Package 1 bare product quantity

1

Packaging without single use plastic

No

Packaging made with recycled cardboard

No

Product name

Acti9 iEM3000

Device short name

iEM3565

Poles description

1P + N|3P + N|3P

Type of measurement

active and reactive energy|active and reactive power|current|voltage

Metering type

active, reactive, apparent energy (signed, four quadrant)

Accuracy class

class 0.5S active energy conforming to IEC 62053-22|class 0.5S active energy conforming to ANSI C12.20

Analogue input type

Rogowski coil 50...5000 A

Network frequency

50 Hz|60 Hz

Technology type

electronic

Display type

LCD display

Sampling rate

32 samples/cycle

Measurement current

50...5000 A

Maximum value measured

99999999.9 kWh|99999999 MWh

Information displayed

tariff (4)

Communication port support

screw terminal block: RS485

Number of inputs

1 digital 0...5 V/11...40 V 24 V DC

Number of outputs

1 digital (static)

Output voltage

5...40 V DC@50 mA

Tightening torque

input/output circuit: 0.5...0.5 N.m Philips screwdriver |voltage circuit: 0.5...0.5 N.m Philips screwdriver |current circuit: 0.8...0.8 N.m pozidriv screwdriver |communication: 0.5...0.5 N.m Philips screwdriver

Compatibility code

iEM3565

Pollution degree

2

Operating altitude

< 3000 m

9 mm pitches

10

Unit type of package 1

PCE

Number of units in package 1

1

Package 1 height

8.8 cm

Package 1 width

9.8 cm

Package 1 length

10.5 cm

Package 1 weight

323 g

Unit type of package 2

S03

Number of units in package 2

30

Package 2 height

30 cm

Package 2 width

30 cm

Package 2 length

40 cm

Package 2 weight

11.483 kg

Unit type of package 3

P06

Number of units in package 3

240

Package 3 height

50 cm

Package 3 width

80 cm

Package 3 length

60 cm

Package 3 weight

100.364 kg

Green premium status for reporting

Green Premium product

Scip number

e00a89f3-4d6c-40b2-8af6-de38ff1e674d

Weee

The product must be disposed on European Union markets following specific waste collection and never end up in rubbish bins

Take-back

No

Take-back

No

Product contributes to saved and avoided emissions

No

Removable battery

N/A
Show all specifications

Documents & downloads

hide show
Filter items
  • All

  • Product Brochures

  • CAD Files and Packs

  • Technical Data Catalogues

  • Other technical guide

  • Installation Instruction

  • End of Life Manual

  • Environmental Disclosure

  • Operating Manuals

  • Technical illustration

  • Declaration of Conformity

  • Certificates (MSDS)