What are the terminal bolt sizes for NSX breakers?

FA276250

30 September 2021

The bolt sizes are provided on the table below.
 
NSX BreakersBolt Size
NSX1006MM BOLT
NSX1608MM BOLT
NSX2508MM BOLT
NSX40010MM BOLT
NSX63010MM BOLT

Some other key features on the NSX range are:
  • Nominal current: 16 to 630 A
  • 6 breaking performances from 25to 150 kA at 415 V
  • Voltage rating: up to 690 V
  • 2 physical sizes from 16 to 630 A
  • 3 and 4-pole versions
  • Isolation with positive break indication
  • Large range of electronic and thermal-magnetic protections
  • Earth leakage protection by associated Vigi Module
  • Measure of main electrical values : I, U, P, E, THD, f, CosF
  •  Wide range of common auxiliaries and accessories interchangeable on site
  • Plug and Play Wiring system and communicating accessories
  • Compliance with international standards: IEC 60947-1 and 2, Nema, IEC 68230 for type 2 Tropicalisation, CCC
  • Compliance with specifications of marine classification companies: Bureau Veritas, Lloyd’s Register of Shipping, Det Norske Veritas, RINA.
For further information please see http://www.schneider-electric.com.au/en/product-range/1887-compact-nsx--630a?xtmc=NSX&xtcr=5
circuit breaker Compact NSX250F, 36 kA at 415 VAC, TMD trip unit 250 A, 3 poles 3d
;