Frequently asked questions
Masterpact and PowerPact: What do the neutral protection (blue dial) settings mean?
FA177265
28 September 2021
Issue:Neutral protection dial settings
Product Line:
Circuit Breakers
Resolution:
Dial settings
4P 3D = Neutral protection is turned off
3P N/2 = Neutral conductor capacity is half that of the line conductors
4P 4D = Neutral conductor capacity is the same as that of the line conductors
1.6N (Neutral conductor capacity is 1.6x that of the line conductors) is also available, but only on 3p breakers.