How to test ground fault from the display of Micrologic 6.2A and E, 6.3A and E trip units.
FA173106
11 April 2022
Issue:
Powerpact H, J and L frame testing Ground fault, trip test, from the display with Micrologic 6.2A and 6.2E, 6.3A and 6.2E trip units.
Product Line:
Powerpact H, J and L frame
Resolution:
Ground fault test instructions:
- Press "mode" button until marker is above the "1/A".
- Then press the arrow key until marker is above the ground symbol.
- Press "ok/test" button and the word "test" will be on the display.
- Press ok/test again to trip the breaker.
- After breaker trips, press ok twice to reset display.