TeSys D, Contactor, TeSys Deca, 3P(3 NO), AC-3/AC-3e, 0 to 440V, 65A, 230VAC 50/60Hz coil

TeSys D, Contactor, TeSys Deca, 3P(3 NO), AC-3/AC-3e, 0 to 440V, 65A, 230VAC 50/60Hz coil

Item Number: LC1D65AP7

Datasheet

Product Dimensions

Width icon

Width55 mm

Height icon

Height122 mm

Depth icon

Depth120 mm

Barcode

Qty UoM EAN Colour
-
-
-

Specifications

Design

Range

TeSys|TeSys Deca

Range of product

TeSys Deca

Product or component type

contactor

Sustainable offer status

Green Premium product

Warranty

18 months

Physical

[ue] rated operational voltage

power circuit: <= 690 V AC 25...400 Hz|power circuit: <= 300 V DC

[ie] rated operational current

80 A (at <60 °C) at <= 440 V AC AC-1 for power circuit|65 A (at <60 °C) at <= 440 V AC AC-3 for power circuit|65 A (at <60 °C) at <= 440 V AC AC-3e for power circuit

Mechanical durability

6 Mcycles

Electrical durability

1.4 Mcycles 80 A AC-1 at Ue <= 440 V|1.45 Mcycles 65 A AC-3 at Ue <= 440 V|1.45 Mcycles 65 A AC-3e at Ue <= 440 V

Connections - terminals

control circuit: screw clamp terminals 2 1-2.5 mm² - cable stiffness: flexible with cable end|control circuit: screw clamp terminals 1 1-4 mm² - cable stiffness: flexible without cable end|control circuit: screw clamp terminals 2 1-4 mm² - cable stiffness: flexible without cable end|control circuit: screw clamp terminals 1 1-4 mm² - cable stiffness: flexible with cable end|control circuit: screw clamp terminals 1 1-4 mm² - cable stiffness: solid without cable end|control circuit: screw clamp terminals 2 1-4 mm² - cable stiffness: solid without cable end|power circuit: screw connection 1 1-35 mm² - cable stiffness: flexible without cable end|power circuit: screw connection 2 1-25 mm² - cable stiffness: flexible without cable end|power circuit: screw connection 1 1-35 mm² - cable stiffness: flexible with cable end|power circuit: screw connection 2 1-25 mm² - cable stiffness: flexible with cable end|power circuit: screw connection 1 1-35 mm² - cable stiffness: solid without cable end|power circuit: screw connection 2 1-25 mm² - cable stiffness: solid without cable end

Insulation resistance

> 10 MOhm for signalling circuit

Mounting support

rail|plate

Standards

EN 60947-4-1|EN 60947-5-1|IEC 60947-4-1|IEC 60947-5-1|CSA C22.2 No 14|UL 60947-4-1|IEC 60335-2-40:Annex JJ|UL 60335-2-40:Annex JJ|IEC 60335-1:Clause 30.2

Product certifications

CCC|UL|CB Scheme|CSA|CE|UKCA|Marine|EAC

Ip degree of protection

IP20 front face conforming to IEC 60529

Climatic withstand

conforming to IACS E10 exposure to damp heat| conforming to IEC 60947-1 Annex Q category D exposure to damp heat

Height

122 mm

Width

55 mm

Depth

120 mm

Net weight

0.86 kg

Reach regulation

Free of Substances of Very High Concern above the threshold

Reach free of svhc

Yes

Eu rohs directive

Compliant

Toxic heavy metal free

Yes

Mercury free

Yes

Rohs exemption information

Yes

China rohs regulation

 Pro-active China RoHS declaration (out of China RoHS legal scope)

Environmental disclosure

ENVPEP1503009EN

Circularity profile

ENVEOLI1503009EN

California proposition 65

WARNING: This product can expose you to chemicals including: Antimony oxide & Antimony trioxide, which is known to the State of California to cause cancer. For more information go to www.P65Warnings.ca.gov

Others

Life cycle assessment data

Yes

Substance regulation data deliverable

Yes

Package 1 bare product quantity

1

Device short name

LC1D

Contactor application

resistive load|motor control

Utilisation category

AC-4|AC-1|AC-3|AC-3e

Poles description

3P

[uc] control circuit voltage

230 V AC 50/60 Hz

Motor power kw

11 kW at 400 V AC 50/60 Hz (AC-4)|18.5 kW at 220...230 V AC 50/60 Hz (AC-3)|30 kW at 380...400 V AC 50/60 Hz (AC-3)|37 kW at 500 V AC 50/60 Hz (AC-3)|37 kW at 660...690 V AC 50/60 Hz (AC-3)|18.5 kW at 220...230 V AC 50/60 Hz (AC-3e)|30 kW at 380...400 V AC 50/60 Hz (AC-3e)|37 kW at 500 V AC 50/60 Hz (AC-3e)|37 kW at 660...690 V AC 50/60 Hz (AC-3e)

Motor power hp

40 hp at 460/480 V AC 50/60 Hz for 3 phases motors|5 hp at 115 V AC 50/60 Hz for 1 phase motors|10 hp at 230/240 V AC 50/60 Hz for 1 phase motors|20 hp at 200/208 V AC 50/60 Hz for 3 phases motors|20 hp at 230/240 V AC 50/60 Hz for 3 phases motors|50 hp at 575/600 V AC 50/60 Hz for 3 phases motors

Compatibility code

LC1D

Pole contact composition

3 NO

Protective cover

with

[ith] conventional free air thermal current

10 A (at 60 °C) for signalling circuit|80 A (at 60 °C) for power circuit

Irms rated making capacity

140 A AC for signalling circuit conforming to IEC 60947-5-1|250 A DC for signalling circuit conforming to IEC 60947-5-1|1000 A at 440 V for power circuit conforming to IEC 60947

Rated breaking capacity

1000 A at 440 V for power circuit conforming to IEC 60947

[icw] rated short-time withstand current

640 A 40 °C - 10 s for power circuit|900 A 40 °C - 1 s for power circuit|110 A 40 °C - 10 min for power circuit|260 A 40 °C - 1 min for power circuit|100 A - 1 s for signalling circuit|120 A - 500 ms for signalling circuit|140 A - 100 ms for signalling circuit

Associated fuse rating

10 A gG for signalling circuit conforming to IEC 60947-5-1|125 A gG at <= 690 V coordination type 1 for power circuit|125 A gG at <= 690 V coordination type 2 for power circuit

Average impedance

1.5 mOhm - Ith 80 A 50 Hz for power circuit

Power dissipation per pole

9.6 W AC-1|6.3 W AC-3|6.3 W AC-3e

[ui] rated insulation voltage

power circuit: 600 V CSA certified|power circuit: 600 V UL certified|signalling circuit: 690 V conforming to IEC 60947-1|signalling circuit: 600 V CSA certified|signalling circuit: 600 V UL certified|power circuit: 690 V conforming to IEC 60947-4-1

Overvoltage category

III

Pollution degree

3

[uimp] rated impulse withstand voltage

6 kV conforming to IEC 60947

Safety reliability level

B10d = 1369863 cycles contactor with nominal load conforming to EN/ISO 13849-1|B10d = 20000000 cycles contactor with mechanical load conforming to EN/ISO 13849-1

Control circuit type

AC at 50/60 Hz standard

Coil technology

without built-in suppressor module

Control circuit voltage limits

0.3...0.6 Uc (-40-70 °C):drop-out AC 50/60 Hz|0.8...1.1 Uc (-40-60 °C):operational AC 50 Hz|0.85...1.1 Uc (-40-60 °C):operational AC 60 Hz|1...1.1 Uc (60-70 °C):operational AC 50/60 Hz

Inrush power in va

140 VA 60 Hz cos phi 0.75 (at 20 °C)|160 VA 50 Hz cos phi 0.75 (at 20 °C)

Hold-in power consumption in va

13 VA 60 Hz cos phi 0.3 (at 20 °C)|15 VA 50 Hz cos phi 0.3 (at 20 °C)

Heat dissipation

4...5 W at 50/60 Hz

Operating time

4...19 ms opening|12...26 ms closing

Maximum operating rate

3600 cyc/h 60 °C

Maximum operating rate

3600 cyc/h at 60 °C

Tightening torque

control circuit: 1.7 N.m - on EverLink BTR screw connectors - with screwdriver flat Ø 6 mm|control circuit: 1.7 N.m - on EverLink BTR screw connectors - with screwdriver Philips No 2|power circuit: 8 N.m - on EverLink BTR screw connectors - cable 25-35 mm² hexagonal screw head 4 mm|power circuit: 5 N.m - on EverLink BTR screw connectors - cable 1-25 mm² hexagonal screw head 4 mm|control circuit: 1.7 N.m - on EverLink BTR screw connectors - with screwdriver pozidriv No 2|power circuit: 2.5 N.m - on EverLink BTR screw connectors - with screwdriver pozidriv No 2

Auxiliary contact composition

1 NO + 1 NC

Auxiliary contacts type

type mechanically linked 1 NO + 1 NC conforming to IEC 60947-5-1| type mirror contact 1 NC conforming to IEC 60947-4-1

Signalling circuit frequency

25...400 Hz

Minimum switching voltage

17 V for signalling circuit

Minimum switching current

5 mA for signalling circuit

Non-overlap time

1.5 ms on de-energisation between NC and NO contact|1.5 ms on energisation between NC and NO contact

Contact compatibility

M2

Protective treatment

TH conforming to IEC 60068-2-30

Permissible ambient air temperature around the device

-40...60 °C|60...70 °C with derating

Operating altitude

0...3000 m

Fire resistance

850 °C conforming to IEC 60695-2-1

Flame retardance

V1 conforming to UL 94

Mechanical robustness

vibrations contactor open (2 Gn, 5...300 Hz) |vibrations contactor closed (4 Gn, 5...300 Hz) |shocks contactor closed (15 Gn for 11 ms) |shocks contactor open (10 Gn for 11 ms)

Unit type of package 1

PCE

Number of units in package 1

1

Package 1 height

6.3 cm

Package 1 width

13.8 cm

Package 1 length

15.5 cm

Package 1 weight

921.0 g

Unit type of package 2

S02

Number of units in package 2

10

Package 2 height

15.0 cm

Package 2 width

30.0 cm

Package 2 length

40.0 cm

Package 2 weight

9.936 kg

Unit type of package 3

P06

Number of units in package 3

160

Package 3 height

77.0 cm

Package 3 width

80.0 cm

Package 3 length

60.0 cm

Package 3 weight

167.14 kg

Weee

The product must be disposed on European Union markets following specific waste collection and never end up in rubbish bins

Pvc free

Yes
Show all specifications

Documents & downloads

hide show
Filter items
  • All

  • CAD Files and Packs

  • Technical Data Catalogues

  • Installation Instruction

  • End of Life Manual

  • Environmental Disclosure

  • Data Bulletin

  • Technical Drawing

  • Declaration of Conformity

  • Certificates (MSDS)

  • eTechPub