Acti9, Residual current breaker with overcurrent protection (RCBO), iDPN N Vigi, 1P+N, 16A, C curve, 6000A, A type, 30mA

Home ProductsCircuit ProtectionActi 9Residual current breaker with overcurrent protection (RCBO)

Acti9, Residual current breaker with overcurrent protection (RCBO), iDPN N Vigi, 1P+N, 16A, C curve, 6000A, A type, 30mA

Item Number: A9D32616

Datasheet

Product Dimensions

Width icon

Width36 mm

Height icon

Height85 mm

Depth icon

Depth73 mm

Barcode

Qty UoM EAN Colour
-
-
-

Specifications

Design

Range of product

iDPN Vigi

Range

Acti9

Product or component type

residual current breaker with overcurrent protection (RCBO)

Device application

distribution

Market segment

small commercial|residential

Sustainable offer status

Green Premium product

Warranty

18 months

Physical

[in] rated current

16 A

[ue] rated operational voltage

230...240 V AC 50 Hz

Control type

toggle

Local signalling

ON, OFF, fault trip

Mounting mode

clip-on

Mounting support

DIN rail

Height

85 mm

Width

36 mm

Depth

73 mm

Net weight

125 g

Mechanical durability

20000 cycles

Electrical durability

20000 cycles

Connections - terminals

single terminal top or bottom 1-16 mm² rigid|single terminal top or bottom 1-10 mm² flexible|single terminal top or bottom 1-10 mm² flexible with ferrule

Wire stripping length

15 mm for top or bottom connection

Standards

EN/IEC 61009-2-1

Product certifications

VDE|KEMA|RCM

Ip degree of protection

IP20 conforming to IEC 60529|IP40 (modular enclosure) conforming to IEC 60529

Relative humidity

95 % at 55 °C

Ambient air temperature for operation

-25...60 °C

Ambient air temperature for storage

-40...85 °C

Reach regulation

Reference contains Substances of Very High Concern above the threshold

Eu rohs directive

Compliant with Exemptions

Mercury free

Yes

Rohs exemption information

Yes

China rohs regulation

Product out of China RoHS scope. Substance declaration for your information

Environmental disclosure

ENVPEP2306032EN

Circularity profile

ENVEOLI2306032

Others

Package 1 bare product quantity

1

Package 2 bare product quantity

54

Package 3 bare product quantity

432

Product name

Acti9 iDPN Vigi

Device short name

iDPN N Vigi

Poles description

1P + N

Number of protected poles

1

Neutral position

left

Network type

AC

Trip unit technology

thermal-magnetic

Curve code

C

Earth-leakage sensitivity

30 mA

Earth-leakage protection time delay

instantaneous

Earth-leakage protection class

type A

Breaking capacity

6000 A Icn at 230...240 V AC 50 Hz conforming to EN/IEC 61009-2-1

Suitability for isolation

yes conforming to EN/IEC 60947-2

Device location in system

outgoer

Network frequency

50 Hz

Magnetic tripping limit

5...10 x In

Residual current tripping technology

voltage independent

[ics] rated service breaking capacity

6000 A 100 % x Icn at 230...240 V AC 50 Hz conforming to EN/IEC 61009-2-1

Rated breaking and making capacity

Idm 6000 A at 230...240 V AC 50 Hz conforming to EN/IEC 61009-2-1

Limitation class

3 conforming to EN/IEC 61009-2-1

[ui] rated insulation voltage

400 V AC 50 Hz

[uimp] rated impulse withstand voltage

4 kV

Contact position indicator

yes

Comb busbar and distribution block compatibility

top or bottom: YES

Connection pitch

9 mm between phase and neutral

9 mm pitches

4

Locking options description

padlocking device

Tightening torque

2 N.m top or bottom

Earth-leakage protection

integrated

Compatibility code

iDPN

Pollution degree

3

Overvoltage category

III conforming to IEC 60364

Electromagnetic compatibility

8/20 µs impulse withstand, 250 A conforming to EN/IEC 61009-2-1

Tropicalisation

2 conforming to IEC 60068-1

Unit type of package 1

PCE

Number of units in package 1

1

Package 1 height

4.0 cm

Package 1 width

8.5 cm

Package 1 length

10.0 cm

Package 1 weight

218 g

Unit type of package 2

S03

Number of units in package 2

54

Package 2 height

30.0 cm

Package 2 width

30.0 cm

Package 2 length

40.0 cm

Package 2 weight

12.213 kg

Unit type of package 3

P12

Number of units in package 3

432

Package 3 height

44.4 cm

Package 3 width

80 cm

Package 3 length

120 cm

Package 3 weight

109.704 kg

Weee

The product must be disposed on European Union markets following specific waste collection and never end up in rubbish bins

Halogen content performance

Halogen free plastic parts product
Show all specifications

Documents & downloads

hide show
Filter items
  • All

  • CAD Files and Packs

  • End of Life Manual

  • Environmental Disclosure

  • Operating Manuals

  • Certificates (MSDS)

  • Declaration of Conformity

Frequently Asked Questions

hide show

What is the difference between A9D32620 and A9D33620 RCBO Acti 9 devices?

 
 

A9D33620 = SI (Super Immunised)
A9D32620 = Type A (AC or pulsating DC)
Type A RCBO = Tripping is ensured for residual sinusoidal alternating currents and residual pulsating direct currents, whether suddenly applied or slowly rising.
Type Si RCBO = With all the features of a Type A device, “Si” type Super Immunised earth leakage protection range has been specially developed to be used with loads or in environments causing disturbances. Examples are lightning or switching surges, harmonics generated by increasing number of loads and constant load leakage current from electronic ballasts, speed drives, computers, etc. The Si increases safety and allows improved continuity of supply.