Acti9, Residual current breaker with overcurrent protection (RCBO), iC60H RCBO, 1P + Ns, 20A, 30mA, A type, 10000A

Home ProductsCircuit ProtectionActi 9Residual current breaker with overcurrent protection (RCBO)

Acti9 Residual current breaker with overcurrent protection (RCBO)

Item Number: A9D11820

Retail
$187
RRP (Inc. GST)

Datasheet

PDF datasheet

For A9D11820

Product Dimensions

Width icon

Width18 mm

Height icon

Height110 mm

Depth icon

Depth77.5 mm

Barcode

Qty UoM EAN Colour
1 3606480558627 -

Specifications

Design

Range

Acti9

Product or component type

residual current breaker with overcurrent protection (RCBO)

Physical

[in] rated current

20 A at 50 °C

[ue] rated operational voltage

230/240 V AC 50/60 Hz

Control type

toggle

Local signalling

ON/OFF indication

Mounting mode

clip-on

Mounting support

DIN rail

Height

110 mm

Width

18 mm

Depth

77.5 mm

Net weight

205 g

Mechanical durability

20000 cycles

Electrical durability

5000 cycles

Connections - terminals

screw clamp terminal (top) 1-25 mm² rigid without cable end|screw clamp terminal (top) 1-16 mm² flexible|screw clamp terminal (bottom) 1-16 mm² rigid without cable end|screw clamp terminal (bottom) 1-10 mm² flexible

Wire stripping length

power circuit: 13 mm for bottom connection|power circuit: 14 mm for top connection

Standards

AS/NZS 61009.1|IEC 61009-1|BS EN 61009-1|IEC 61009-2-2

Ip degree of protection

IP20

Relative humidity

95 % at 55 °C

Ambient air temperature for operation

-15...60 °C

Ambient air temperature for storage

-40...85 °C

Reach regulation

Reference contains Substances of Very High Concern above the threshold

Eu rohs directive

Not compliant

China rohs regulation

Product out of China RoHS scope. Substance declaration for your information

Environmental disclosure

ENVPEP121008EN

Circularity profile

N/A
Show all specifications

Documents & downloads

hide show
Filter items
  • All

  • CAD Files and Packs

  • Environmental Disclosure

  • Installation Instruction

  • Certificates (MSDS)

  • Declaration of Conformity

  • Page 2  /  2

Frequently Asked Questions

hide show

What is the replacement for a Merlin Gerin 26860, RCBO, 240V, 20A, 30mA?

The replacement for a Merlin Gerin 26860, RCBO, 240V, 20A, 30mA is a A9D11820.
See link for further details:
https://www.se.com/au/en/product/A9D11820/ic60h---earth-leakage-circuit-breaker---1p-%2B-n---c-curve---20-a---30-ma---240-v/
A9D11820 Product picture

What is the replacement for 26860 RCBO?

The replacement for 26860 is A9D11820

For more information see attachment and link:https://www.se.com/au/en/product/A9D11820/ic60h---earth-leakage-circuit-breaker---1p-%2B-n---c-curve---20-a---30-ma---240-v/